MCAC-ATSM-2013-11 Aqua Tempo Power Series (with LAK) air cooled scroll chiller unit (50Hz)
137
27
Input of transformer, 220-230V AC current. (Only valid for the main unit).
28
Input of three-phase four-wire power supply (Fault code E1).
Three phases A, B and C of power supply should exist simultaneously, and the difference of phase angle should be 120º
among them. If the conditions are not met, fault of phase sequence or phase lack may occur, and fault code will be displayed.
When the power supply returns to normal condition, fault is removed. Attention: phase lace and phase dislocation of power
supply are detected only in the early period after the power supply is connected, and they are not detected while the unit is in
operation.
29
Output of transformer.
30
Power port for the current board.
31
One compressor of the system B(B2).
Neutral wire.
One compressor of the system A(A2).
Neutral wire.
32
The alarm signal output of the unit(ON/OFF signal)
33
Anti-freezing pressure protection of the system A(Protection code Pc)
Anti-freezing pressure protection of the system B(Protection code Pd)
34
Remote control port(ON/OFF signal, effect on NO.0 unit)
1.Dial the code S7 in the main control board to the
”ON” position and enter to the remote control mode
(the wired controller is invalid)
2.If the port is closed, the unit is turned on, else, the unit is turned off.
35
Remote mode control port(ON/OFF signal effect on NO.0 unit)
1.Dial the code S7 in the main control board to the
“
ON
”
position and enter to the remote control mode (The wired controller
is invalid).
2.First, the ON/OFF port is closed. Second, if this port is closed, the unit enters the heating mode, else, the unit enters
the cooling mode.
CAUTION
1. Faults
When the main unit suffers faults, the main unit stops operating, and all other units also stop running;
When the subordinate unit suffers faults, only the unit stops operating, and other units are not affected.
2. Protection
When the main unit is under protection, only the unit stops operating, and other units keep running;
When the subordinate unit is under protection, only the unit stops operating, and other units are not affected.
Содержание Aqua Tempo Super Series
Страница 37: ...Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz MCAC ATSM 2013 11 36 130kW module...
Страница 38: ...MCAC ATSM 2013 11 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 37 200kW module...
Страница 39: ...Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz MCAC ATSM 2013 11 38 250kW module...
Страница 45: ...Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz MCAC ATSM 2013 11 44 200kW module...
Страница 48: ......
Страница 62: ...MCAC ATSM 2013 11 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 61...
Страница 69: ...Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz MCAC ATSM 2013 11 68...
Страница 71: ...Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz MCAC ATSM 2013 11 70 MGBL D65W RN1...
Страница 72: ...MCAC ATSM 2013 11 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 71...
Страница 74: ...MCAC ATSM 2013 11 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 73 10 4 MGBL F130W RN1...
Страница 77: ...Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz MCAC ATSM 2013 11 76 10 5 MGBL F200W RN1...
Страница 80: ...MCAC ATSM 2013 11 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 79 10 6 MGBL F250W RN1...
Страница 100: ...MCAC ATSM 2013 11 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 99 55 60 65kW module 130kW module...