Midea 190RDN3-E Скачать руководство пользователя страница 11

8

Installation & Owner‘s Manual

NOTE

While the ambient temperature is below 5

,  heat pump 

efficiency will decrease dramatically, the unit will automatically 

shift to E-heater mode.

  About TCO and ATCO

The  power  of  compressor  and  E-heater  will  be  automatically 

shut-off or turn on by TCO and ATCO.

● 

 If the water temperature is higher than 78

, the ATCO will automati-

cally shut off the power of compressor and E-heater, and turn it on 

it if the temperature fall down below 68

.

  If the water temperature is higher than 85

, the TCO will automati-

cally shut off the power of compressor and E-heater, it must be 

reset by an authorised service technician.

  

Restart After a Long Term Stop

When the unit is restarted after a long term stop (trail running 

included), it is normal that outlet water is unclean. Turn the tap on 

and the water will be flushed clean.

5.2.3  Basic function

1)  Weekly disinfect function

Under disinfection mode, unit immediately starts to heat water up 

to 65

 to kill any potential of legionella bacteria inside  water of 

tank

,

     icon will light on the display screen during disinfection; 

Unit will quit disinfection mode when water temperature is higher 

than 65

 and extinguish      icon.

2)  How to turn on the unit:

I

f unit is OFF->press           ->button will be unlocked ->press 

        to select mode  ->press             to set target water 
temperature->press           ->unit will automatically select mode 
and start to heat water to target temperature.

Fig.5-4

500

1000

1500

2000

2500

3000

5

7

15 20 25 30 32 35 40 43

C

ap

ac

ity

(W

)

Ambient temp(

)

15-45

15-55

15-65

Fig.5-5

1

2

3

4

5

6

7

5

7

15

20

25

30

32

35

40

43

C

O

P(W/W)

Ambient  temp(

)

15-45

15-55

15-65

Fig.5-6

0 : 00: 00

2 : 24: 00

4 : 48: 00

7 : 12: 00

9 : 36: 00

12: 00: 00

14: 24: 00

5

7

15 20 25 30 32 35 40 43

Ti

m

e(

h)

Ambient  temp(

)

15-45

15-55

15-65

Содержание 190RDN3-E

Страница 1: ...ATION OWNER S MANUAL Thank you very much for purchasing our product Before using your unit please read this manual carefully and keep it for future reference ALL IN ONE Type Air source Heat Pump Water...

Страница 2: ...loding Continuous leakage of water from the valve may indicate a problem with the water heater THE INSTALLATION MUST COMPLY WITH THE REQUIREMENTS OF AS NZS 3500 4 AS NZS 3000 and all local codes and r...

Страница 3: ...anual When ordering repair parts please always give the following information 1 Model serial and product number 2 Part name on location Fan Assy PTR Valve Top Cover Evaporator Filter Magnesian Stick R...

Страница 4: ...should be supervised to ensure that they do not play with the appliance NOTE Above calculations are based on ideal conditions the final amount will be different the actual running will vary with condi...

Страница 5: ...be installed on a metal part of building make sure the electric insulation meets the relevant local electric standard 75 Gradient limit 75 CAUTION The earthing pole of socket must be well grounded ma...

Страница 6: ...equire the water piping conden sate piping and drain piping to be insulated to shelter agianst freezing CAUTION CAUTION WARNING The unit must be securely fixed otherwise noise and vibartion may result...

Страница 7: ...heat resistant and durable 2 Installation of the pipe for PTR valve The valve connecting thread is RC3 4 internal thread After installation it must be confirmed that the drainpipe outlet is exposed i...

Страница 8: ...drain vent is at the lowest place Recommended inclination angle of unit to the ground should be no more than 2 Set the electric leakage protector according to the relevant electric technical standard...

Страница 9: ...re found in aerosol sprays detergents bleaches cleaning solvents air fresheners paint and varnish removers refrigerants and many other commercial and household products In addition excessive dust and...

Страница 10: ...e system will defrost automatically to keep effective performance about 5 15min At defrosting time the compressor will stop but fan motor will still run Heat up Time There are different heat up times...

Страница 11: ...tlet water is unclean Turn the tap on and the water will be flushed clean 5 2 3 Basic function 1 Weekly disinfect function Under disinfection mode unit immediately starts to heat water up to 65 to kil...

Страница 12: ...heater Mode is selected at the off time ALARM When unit is displaying protection error will flash with 5Hz frequency as well as buzzer sounding 3 times every minute until protection error eliminated o...

Страница 13: ...e will be extinguished CLOCK will be displayed all the time shows current clock on normal time shows setting clock when setting timer TIME CONFLICT Reserved function will be displayed if the timer whi...

Страница 14: ...or more than 3 seconds and the Timer TIME ON TIME OFF function will be canceled INCREASE UP If button is unlocked corresponding value will increase by pushing When setting temperature press for more t...

Страница 15: ...3 1 2 3 6 4 Auto restart If power is disconnected the unit can remember some of the setting parameters On or Off state operating mode setting water tempera ture when it re powers on the unit will be o...

Страница 16: ...son to service the unit If PCB current_induction_circuit check the current difference between L N 14mA system consider it as electric leakage error Electric leakage error Compressor suction temperatur...

Страница 17: ...draining exit The min heat resistance of the drain pipe is not less than 93 if the drain pipe can not meet the requirement please open the cold water inlet valve open the hot water tap until there is...

Страница 18: ...e 40W Air out from sideward 440W 2150W 1 0MPa DN20 DN20 DN20 DN20 Default 63 38 70 adjustable T20A 250VAC 568 1580mm 190L 90kg 2780W 12 1A 1500W 2150W Water pipeline system RSJ 15 190RDN3 E Table 9 1...

Страница 19: ...ult or defect in the installation of the heat pump 3 If corrosion has occurred because the anode has not been changed in accordance with the owner s manual 4 If a cold water expansion valve check valv...

Страница 20: ...MDV11IU 055BW DZ 2020001A9998...

Отзывы: