Midea 190RDN3-E Скачать руководство пользователя страница 10

7

Installation & Owner‘s Manual

 

Fig.5-2

Emptying

Drainpipe shut-off valve

Close

After emptying, please replace the nut of 

drainpipe.

5.2 Trial- running

5.2.1 Check list before commissioning. 

1)  Check list before trial-running.
2)  Correct installation of the system.
3)  Correct connection of  water/air piping and wiring.
4)  Condensate draining smoothly well insulated for all hydraulic 

part.

5)  Correct power supply.
6)  No air in the

 

water pipeline and all valves opened.

7)  Effective RCD installed.

8)  Sufficient inlet water pressure (between 0.15MPa and 0.65MPa) 

     (150-650kPa).

5.2.2 About Running

1)  System Structure Figure

This unit has two kinds of heat sources: Heat pump 

(compressor) and electric heater.

The unit will automatically select heat sources to heat water to 

the target temperature in different mode.

2)  Water Temperature Display

The temperature shown on the display depends on the water 

temperature sensor. It is normal that sometimes the display tempera-

ture decreases while the unit is running, it is caused when the 

natural convection of the upper hot wate mixes with by the bottom 

cold water which flows from inlet tap.

3)  

Operating mode should be selected manually. Refer to table 5-1.

Running Temperature Range

Water temperature limits:

    Tank

Water temperature sensor

Electric heater

Water inlet

Water outlet

Fig.5-3

  Defrosting During Water-heating 

In heat pump running period, if the evaporator becomes frosted in 

lower ambient temperature, the system will defrost automatically 

to keep effective performance (about 5~15min). At defrosting time, 

the compressor will stop, but fan motor will still run.

④ 

Heat-up Time 

There are different heat-up times at different ambient tempera-

tures. Normally lower ambient temperature result in longer heat-up 

times because of lower effective performance.

4)  Heat Source Shift

 

The default heating source is heat pump. 

If ambient temperature range is out of heat pump operating range, 

heat pump will stop running, the unit will shift automatically to activate 

E-heater and show the icon LA on the display, then if the ambient 

temperature goes into the running range of heat pump again, it will 

stop E-heater and shift automatically to heat pump again, and the 

icon LA will be extinguished.

 

If the target water temperature is higher than maxinum tempera-

ture (Heat pump), the unit will activate heat pump firstly to the 

maxinum temperature, then stop heat pump, activate E-heater to 

continually heat water to the target temperature.

NOTE

If only using E-heater mode, approx 60% of the tank water will be 

heated, so set a higher target water temperature if the ambient 

temperature is out of the heat pump running range.

NOTE

If the system continuously reports heat pump protection, the latest 

error code  and      will be shown on the display, then heat pump will 

stop running, and the unit will shift automatically to E-heater mode 

as the backup mode, but the code  and       will be shown until power 

is reset.

--

65

Ambient temp. 

range

Maxinum 

temp.

(Heat pump)

Table 5-1

Setting temp. 

range

Operation 

mode

Economy mode

Hybrid mode

E-heater mode

5~43

-20~43

-20~43

38~70

38~65

38~70

65

Содержание 190RDN3-E

Страница 1: ...ATION OWNER S MANUAL Thank you very much for purchasing our product Before using your unit please read this manual carefully and keep it for future reference ALL IN ONE Type Air source Heat Pump Water...

Страница 2: ...loding Continuous leakage of water from the valve may indicate a problem with the water heater THE INSTALLATION MUST COMPLY WITH THE REQUIREMENTS OF AS NZS 3500 4 AS NZS 3000 and all local codes and r...

Страница 3: ...anual When ordering repair parts please always give the following information 1 Model serial and product number 2 Part name on location Fan Assy PTR Valve Top Cover Evaporator Filter Magnesian Stick R...

Страница 4: ...should be supervised to ensure that they do not play with the appliance NOTE Above calculations are based on ideal conditions the final amount will be different the actual running will vary with condi...

Страница 5: ...be installed on a metal part of building make sure the electric insulation meets the relevant local electric standard 75 Gradient limit 75 CAUTION The earthing pole of socket must be well grounded ma...

Страница 6: ...equire the water piping conden sate piping and drain piping to be insulated to shelter agianst freezing CAUTION CAUTION WARNING The unit must be securely fixed otherwise noise and vibartion may result...

Страница 7: ...heat resistant and durable 2 Installation of the pipe for PTR valve The valve connecting thread is RC3 4 internal thread After installation it must be confirmed that the drainpipe outlet is exposed i...

Страница 8: ...drain vent is at the lowest place Recommended inclination angle of unit to the ground should be no more than 2 Set the electric leakage protector according to the relevant electric technical standard...

Страница 9: ...re found in aerosol sprays detergents bleaches cleaning solvents air fresheners paint and varnish removers refrigerants and many other commercial and household products In addition excessive dust and...

Страница 10: ...e system will defrost automatically to keep effective performance about 5 15min At defrosting time the compressor will stop but fan motor will still run Heat up Time There are different heat up times...

Страница 11: ...tlet water is unclean Turn the tap on and the water will be flushed clean 5 2 3 Basic function 1 Weekly disinfect function Under disinfection mode unit immediately starts to heat water up to 65 to kil...

Страница 12: ...heater Mode is selected at the off time ALARM When unit is displaying protection error will flash with 5Hz frequency as well as buzzer sounding 3 times every minute until protection error eliminated o...

Страница 13: ...e will be extinguished CLOCK will be displayed all the time shows current clock on normal time shows setting clock when setting timer TIME CONFLICT Reserved function will be displayed if the timer whi...

Страница 14: ...or more than 3 seconds and the Timer TIME ON TIME OFF function will be canceled INCREASE UP If button is unlocked corresponding value will increase by pushing When setting temperature press for more t...

Страница 15: ...3 1 2 3 6 4 Auto restart If power is disconnected the unit can remember some of the setting parameters On or Off state operating mode setting water tempera ture when it re powers on the unit will be o...

Страница 16: ...son to service the unit If PCB current_induction_circuit check the current difference between L N 14mA system consider it as electric leakage error Electric leakage error Compressor suction temperatur...

Страница 17: ...draining exit The min heat resistance of the drain pipe is not less than 93 if the drain pipe can not meet the requirement please open the cold water inlet valve open the hot water tap until there is...

Страница 18: ...e 40W Air out from sideward 440W 2150W 1 0MPa DN20 DN20 DN20 DN20 Default 63 38 70 adjustable T20A 250VAC 568 1580mm 190L 90kg 2780W 12 1A 1500W 2150W Water pipeline system RSJ 15 190RDN3 E Table 9 1...

Страница 19: ...ult or defect in the installation of the heat pump 3 If corrosion has occurred because the anode has not been changed in accordance with the owner s manual 4 If a cold water expansion valve check valv...

Страница 20: ...MDV11IU 055BW DZ 2020001A9998...

Отзывы: