Chapter 4: Using the Command Line Interface
156
Sensor types
Description
airPressure
Air pressure sensors
airFlow
Air flow sensors
vibration
Vibration sensors
•
<value> is the value for the specified threshold of the specified sensor type. Note that diverse sensor types use
different measurement units.
Sensor types
Measurement units
absoluteHumidity
g/m^3 (that is, g/m
3
)
relativeHumidity
%
temperature
Degrees Celsius ( ) or Fahrenheit ( ), depending on your measurement unit
settings.
airPressure
Pascal (Pa) or psi, depending on your measurement unit settings.
airFlow
m/s
vibration
g
•
<hy_value> is the deassertion hysteresis value applied to the specified sensor type.
•
<as_value> is the assertion timeout value applied to the specified sensor type. It ranges from 0 to 100 (samples).
Example - Default Upper Thresholds for Temperature
It is assumed that your preferred measurement unit for temperature is set to degrees Celsius. Then the following command
sets the default Upper Warning threshold to 20 and Upper Critical threshold to 24 for all temperature sensors.
config:#
defaultThresholds temperature upperWarning 20 upperCritical 24
Sensor Threshold Configuration Commands
A sensor configuration command begins with
sensor
. You can use the commands to configure the threshold, hysteresis
and assertion timeout values for any sensor associated with the following items:
•
Outlets
•
Inlets
•
Overcurrent protectors