DOC 4380A
4380A O & M Manual
54
098-00723-000
– Jul 2017 Revision 4.0
SyncSystem 4380A O&M Manual
[active] false
[occurrences] 0
L.
The [ref_unlocked] fields are reporting the clock status and system performance information. The
reference should be locked ([ref_unlocked] [active] = false). The syscfg active block should be
false. TCXO should also not be reporting any errors.
[ref_unlocked]
[active] false
[occurrences] 0
[syscfg]
[active] false
[occurrences] 0
[tcxo_failure]
[active] false
[occurrences] 0
M.
Once the system obtains a sufficient amount of clock data the kas2 values will be
available.
[kas2]
[aging] 1.034079545296274e-21
[coldstart_time] 2015-08-05T14:34:30Z
[deviation_scalar] 1.00000000000
[frequency] -1.498015356088144e-13
[phase] 1.390605625690108e-09
[ptd] 8.827366060000000e-10
[steer] -2.226820215582848e-10
[warmstart_time] N/A
N.
The leap seconds block should reflect the current # of leap seconds -10. The effective time should
reflect the # of seconds since 1970 the current leap second occurred. The future leap second value
should equal the current value unless there is a leap second pending.
[leapseconds]
[current] 35
[effectivity_time] 2014-01-01-00:00:00
[future] 35
O.
The system should show that NTP is locked (true) and that the system is using the internal clock.
[ntp]
[locked] true
[source] internal refclock
P.
The system should report the outputs are enabled
[outputs] enabled
Q.
The system will also show if the external & internal clocks have been detected and the system will
provide the internal operating temperature. If an external 10MHz signal is not being provided, the
reference:external
field will display
signal missing.
The
ocxo_freq_control
should also be
between -98 and 98.
Reference_type = hp5071A
[frequency]
[external]
[communications] N/A
[locked] true
[signal] present
[internal]
[locked] true
[timescale]
[clocks]
[Cesium1]
[1_pps_present_slot_4_port_1] true
[communications] N/A
[id] 1365
[Cesium2]
[1_pps_present_slot_4_port_2] true
[communications] N/A
[id] 1559
[hp5071]
Содержание SyncSystem 4380A