MC30-X/10-4
Doc. N°
MO-0350-ING
Copyright 2016
FW: 1211.37.06.x
Date
17.06.2022
Rev.
3
Pag.
24
of
43
5.1.2.6
–
“Operation Logic”
Output Config
= [Pulse, Automatic Reset, Manual Reset]
Automatic
:
In this mode the output relay is “operated” (energized if “
”, deenergized if “
”)
when the controlling Functional Output is activated and it is reset to the “
non operated
”
condition when the Functional Output gets deactivated but, anyhow, not before the time
“
” has elapsed (minimum duration of the operation time)
Manual
:
In this mode the output relay is “operated” when the controlling Functional Output is
activated and remains in the operated condition until a manual reset command is issued
by the relay keyboard (local commands menu) or via the serial communication. In this
mode the timer “
”
has no effect.
Impulsive
:
In this mode the output relay is “operated” when the controlling Functional Output is
activated and it remains in the “operated” condition (energized if “
”, deenergized if
“
”) for the set time “
” independently from the status of the controlling
Functional Output.
5.1.2.7
–
“
Timer -
Operation Time”
This timer controls the duration of the activation of the output relay.
Timer
:
0
(0-10)s, step 0.01s