3.8 - BF (F51BF) - Breaker Failure
FuncEnab
→
Enable
[Disable / Enable]
Options
→
TrR
Relay1
Relay1
–
Relay2
–
Relay3
–
Relay4
TripLev
→
No Param
No Parameters
Timers
→
tBF
0.2
s
(0.05
0.75)
step
0.01
s
Description of variables
FuncEnab
: If disable the function is disactivated
TrR
: Output relay programmed for trip command to the Circuit Breaker
tBF
: Trip time delay
Operation
: If after the time “tBF” from pick
-
up of the programmed relay “TrR” the current measured still
exceeds 5%In, the output relay
associated to the “BF” function is operated (relay another than TrR).
3.9 - I.R.F. - Internal Relay Failure
FuncEnab
→
No Param
No Parameters
Options
→
Opl
NoTrip
[NoTrip / Trip]
TripLev
→
No Param
No Parameters
Timers
→
No Param
No Parameters
Description of variables
Opl
:
The variable “
Opl
”
can be programmed to trip the output relays same as the other
protection functions (Opl = TRIP), or to only operate the “IRF”
signal led without tripping
the output relays (Opl = NoTRIP).
Trip when
: an internal fault in the relay is detected (see Diagnostics)
When the function is tripped
:
Signalization
=
Led “
PWR/I.R.F.
”
blink
Last Trip
= Is recorded
Function reset when
: it returns to normal operation
Led reset when
: Push-button is pressed