3.6 - Io>> (2F51N) - Second Earth Fault protection level
FuncEnab
→
Enable
[Disable / Enable]
Options
→
BI
Disable
[Disable / Enable]
→
Trg
Enable
[Disable / Enable]
TripLev
→
Io>>
0.01
Ion (0.01
9.99)
step 0.01
Ion
Timers
→
tIo>>
0.05
s
(0.05
60)
step
0.01
s
Description of variables
FuncEnab
: If disable the function is disactivated
BI
: Operation controlled by Blocking Digital Input
Trg
: Function operation triggers the oscillographic wave form capture
(see § Oscillographic Recording)
Io>>
: Minimum Zero Sequence Residual Current Pick-up level
tIo>>
: Trip time delay
Trip when
: The current trip level is exceeded for time
“tIo>>”.
When the function is tripped
:
Signalization
=
Led “Trip” is illuminated
Last Trip
= Is recorded
Function reset when
: The current drop below 95% Io>>.
Led reset when
: push-button is pressed
3.7 - IoH (3F51N) - Third Earth Fault protection level
FuncEnab
→
Enable
[Disable / Enable]
Options
→
BI
Disable
[Disable / Enable]
→
Trg
Enable
[Disable / Enable]
TripLev
→
IoH
0.01
Ion (0.01
9.99)
step 0.01
Ion
Timers
→
tIoH
0.05
s
(0.05
60)
step
0.01
s
Description of variables
FuncEnab
: If disable the function is disactivated
BI
: Operation controlled by Blocking Digital Input
Trg
: Function operation triggers the oscillographic wave form capture
(see § Oscillographic Recording)
IoH
: Minimum Zero Sequence Residual Current Pick-up level
tIoH
: Trip time delay
Trip when
:
The current trip level is exceeded for time “tIoH”.
When the function is tripped
:
Signalization
=
Led “Trip” is illuminated
Last Trip
= Is recorded
Function reset when
: The current drop below 95% IoH.
Led reset when
: Push-button is pressed