MC30-X/10-4
Doc. N°
MO-0350-ING
Copyright 2016
FW: 1211.37.06.x
Date
17.06.2022
Rev.
3
Pag.
23
of
43
5.1.2.4
–
“
F
unction”
Select the function for tripping the output relay.
In this list are show the functions that can be associated with digital inputs or output relay.
T>
Ta
Alarm
Thermal Image T>
T>
Trip
I>
I>
Start
First overcurrent element
tI>
Trip
I>>
I>>
Start
Second overcurrent element
tI>>
Trip
IH
IH
Start
Third overcurrent element
tIH
Trip
Io>
Io>
Start
First Earth Fault element
tIo>
Trip
Io>>
Io>>
Start
Second Earth Fault element
tIo>>
Trip
IoH
IoH
Start
Third Earth Fault element
tIoH
Trip
BF
BF
Trip
Breaker Failure
IRF
IRF
Trip
Internal Relay Failure
CBopen
CBopen
Trip
C/B open command
CBclose
CBclose
Trip
C/B close command
HwRecov
HwRecov
Trip
Hardware Recovery
0.D1
Digital Input
“0.D1”
activated
Digital Input on Main Module
0.D1NOT
Digital Input “0.D1”
deactivated
0.D2
Digital Input “0.D2”
activated
0.D2NOT
Digital Input “0.D2”
deactivated
0.D3
Digital Input “0.D3”
activated
0.D3NOT
Digital Input “0.D3”
deactivated
1.D1
Digital Input “1.D1”
activated
Digital Input on Expansion Module
1.D1NOT
Digital Input “1.D1”
deactivated
to
1.D10
Digital Input “1.D10”
activated
1.D10NOT
Digital Input “1.D10”
deactivated
5.1.2.5
–
“Operation Logic”
Operation Logic
= [None, OR, AND]