MC30-X/10-4
Doc. N°
MO-0350-ING
Copyright 2016
FW: 1211.37.06.x
Date
17.06.2022
Rev.
3
Pag.
20
of
43
3.11 - Comm
–
Communication Parameters
FuncEnab
→
No Param
No Parameters
Options
→
LBd
9600
[9600 / 19200 / 38400]
→
RBd
9600
[9600 / 19200]
→
Mod
8,n,1
[8,n,1 / 8,o,1 / 8,e,1]
→
RPr
Modbus
[Iec103 / Modbus]
TripLev
→
No Param
No Parameters
Timers
→
No Param
No Parameters
Description of variables
LBd
: Local Baud Rate (Front panel RS232 communication speed)
RBd
: Remote Baud Rate
(Rear panel terminal blocks RS485 communication speed)
Mod
: Remote mode (communication parameters)
Note
: Any change of this setting becomes valid at the next power on
RPr
: Remote Protocol
3.12 - LCD
–
Display and Buzzer operation
FuncEnab
→
No Param
No Parameters
Options
→
Key
BeepON
[BeepOFF / BeepON]
→
BkL
Auto
[Auto / On]
→
AnF
View
[View / Hidden]
TripLev
→
No Param
No Parameters
Timers
→
No Param
No Parameters
Description of variables
Key
:
Buzzer “Beep” on operation of Keyboard buttons.
BkL
: LCD
Backlight continuously “ON” or switched
-on Automatically on operation of
Keyboard buttons.
AnF
: Field Alarms
View
= Visible if preset an Home page local HMI
Hidden
= Presence not visible on Home page local HMI