5.2.3 CAN Cable
The CAN cable must meet the requirements of ISO11898. The
cable must meet the following specifications:
Tabelle 2: Specifications of CAN bus cable
Parameter
Value
Impedance
108 - 132 Ohm (nom. 120 Ohm)
Specific Resistance
70 mOhm/Meter
Specific Signal Delay
5 ns/Meter
The CAN bus cable is connected to the µCAN.8.dio-BOX module
via terminals inside the case. For the pinning of the terminal refer
to “CAN Bus” on page 26 of this manual.