![MicroControl uCAN.8.dio-BOX Скачать руководство пользователя страница 29](http://html1.mh-extra.com/html/microcontrol/ucan-8-dio-box/ucan-8-dio-box_manual_1786185029.webp)
Installation
Termination
Page
29
MicroControl Version 2.00
μCAN.8.dio-BOX
5
5.7 Termination
The modules at both ends in the CAN network have to be termi-
nated with a resistor of 120 ohms. That means the modules at
the end of the bus line are not reflecting back power and the
communication can not be disturbed.
For termination of the μCAN.8.dio-BOX the "
Term
" switch must
be turned from position "Term Off“ to position "Term On“.
Modul ID
Baud
Term
Off/On
CAN_H
CAN_L
GND
V+
V-PWR
V+PWR
I/O_1
I/O_2
I/O_3
I/O_4
I/O_5
I/O_6
I/O_7
I/O_8
NS
MS
1
2
4
3
6
5
7
8
Termination off
Abb. 10: Termination of CANbus
Please make sure that only the devices at both ends of a CAN bus
Attention !
are terminated.