P341 Technical Data Sheet
24
P341 Software versions 36 & 71J
RP2 Comms Mode:
IEC 60870 FT1.2
IEC 60870 10-Bit No parity
RP2 Address: 0…255
RP2 InactivTimer:
1…30 mins
RP2 Baud Rate:
9600/19200/38400 bits/s
Note:
If RP2 Port Config is K Bus the baud
rate is fixed at 64 kbits/s
Commission tests
Monitor Bit 1:
(up to):
Monitor Bit 8:
Binary function link strings, selecting which
DDB signals have their status visible in the
Commissioning menu, for test purposes
Test Mode:
Disabled
Test Mode
Blocked Contacts
Test Pattern:
Configuration of which output contacts are to
be energized when the contact test is
applied
Circuit breaker condition monitoring
(CB monitor setup)
Broken I^:
1.0…2.0
I^ Maintenance:
Alarm
Disabled/Enabled
I^ Maintenance:
1…25000
I^ Lockout:
Alarm
Disabled/Enabled
I^ Lockout:
1…25000
No. CB Ops Maint:
Alarm
Disabled/Enabled
No. CB Ops Maint:
1…10000
No. CB Ops Lock:
Alarm
Disabled/Enabled
No. CB Ops Lock:
1…10000
CB Time Maint:
Alarm
Disabled/Enabled
CB Time Maint:
0.005…0.500 s
CB Time Lockout:
Alarm
Disabled/Enabled
CB Time Lockout:
0.005…0.500 s
Fault Freq Lock:
Alarm
Disabled/Enabled
Fault Freq Count:
1…9999
Fault Freq Time:
0…9999 s
Opto coupled binary inputs
(opto config)
Global Nominal V:
24 - 27 V
30 - 34 V
48 - 54 V
110 - 125 V
220 - 250 V
Custom
Opto Input 1:
(up to):
Opto Input #. (# = max. opto no. fitted):
Custom options allow independent
thresholds to be set per opto, from the same
range as above.
Opto Filter Control:
Binary function link string, selecting which
optos will have an extra 1/2 cycle noise filter,
and which will not.
Characteristics:
Standard 60% - 80%
50% - 70%
Control inputs into PSL
(Ctrl. I/P config.)
Hotkey Enabled:
Binary function link string, selecting which of
the control inputs will be driven from
Hotkeys.
Control Input 1:
Latched/Pulsed
(up to):
Control Input 32:
Latched/Pulsed
Ctrl Command 1:
(up to):
Ctrl Command 32:
ON/OFF
SET/RESET
IN/OUT
ENABLED/DISABLED
IED configurator
Switch Conf. Bank: No Action/Switch Banks
Restore MCL: No Action, Restore MCL
IEC
61850 GOOSE
GoEna: Disabled/Enabled
Test Mode: Disabled/Pass Through/Forced
VOP Test Pattern: 0x00000000...
0xFFFFFFFF
Ignore Test Flag: No/Yes
Control input user labels
(Ctrl. I/P labels)
Control Input 1:
(up to):
Control Input 32:
User defined text string to describe the
function of the particular control input
Settings in multiple groups
Note:
All settings here onwards apply for
setting groups # = 1 to 4.
Содержание ALSTOM P341
Страница 3: ......
Страница 4: ...0 0 12 3 12 3 4...
Страница 5: ......
Страница 6: ...00 01 1 2 33 1 3 30 30 4...
Страница 7: ...0 1 2 0 0 3 4 5 2 12 3 4 6 3 5 1 0 3 0...
Страница 8: ...0 10 2 0 13 4 2 1 2 3 5 6 6 7 8 8 7 6 9...
Страница 9: ...0 1 2 3 3 234 34 5 6 5 75 8 9...
Страница 10: ...01 21 3 1 4 56 1 0 31 0 31 0 31 7 8 6 9 1 2 3 31 121 7 9 8 6...
Страница 61: ......