background image

 

 

 

 

 

P341 Technical Data Sheet 

22

 

P341 Software versions 36 & 71J  

 

Settings, measurements and 
records list 

Settings list 

Global settings (system data) 

Language: English/French/German/Spanish 
Frequency: 50/60 Hz 

Circuit breaker control 
(CB control): 

CB Control by: 
Disabled 
Local 
Remote 
Local+Remote 
Opto 
Opto+local 
Opto+Remote 
Opto+Rem+local 
Close Pulse Time: 0.10...10.00 s 
Trip Pulse Time: 0.10…5.00 s 
Man Close t max: 0.01…9999.00 s 
Man Close Delay: 0.01…600.00 s 
CB Healthy Time: 0.01…9999.00 s 
Check Sync. Time: 0.01...9999.00 s 
Reset Lockout by: User Interface/CB Close 
Man Close RstDly: 0.10...600.00 s 
CB Status Input: 
None 
52A 
52B 
52A & 52B 

Date and time 

 

IRIG-B Sync:    

Disabled/Enabled 

Battery Alarm:    

Disabled/Enabled       

LocalTime Enable:        Disabled/Fixed/Flexible  
LocalTime Offset:    

 -720 min…720 min            

DST Enable:       

Disabled/Enabled        

DST Offset: 

 

30 min…60 min              

DST Start: 

        

First/Second/Third/ 

   

 

 

Fourth/Last                                 

DST Start Day:  

Sun/Mon/Tues/Wed/   

   

 

 

 Thurs/Fri/Sat                                                  

DST Start Month:  

Jan/Feb/Mar/Apr/ 

  

 

 

May/Jun/ Jul/Aug/ 

  

 

 

Sept/Oct/Nov/Dec  

DST Start Mins:  

0 min…1425 min                

DST End:  

 

First/Second/ 

   

 

 

Third/Fourth/Last                                  

DST End Day:   

Sun/Mon/Tues/Wed/   

   

 

  

Thurs/Fri/Sat                       

 
 
 

 
DST End Month: 

Jan/Feb/Mar/Apr 

  

 

 

/May/Jun/Jul/Aug/ 

  

 

 

Sept/Oct/Nov/Dec  

DST End Mins:  

0 min…1425 min                  

RP1 Time Zone: 

UTC/Local                       

RP2 Time Zone:       

UTC/Local                                

Tunnel Time Zone:   

UTC/Local   

Configuration  

Setting Group: 
  Select via Menu 
  Select via PSL 
Active Settings:  

Group 1/2/3/4 

Setting Group 1: 

Disabled/Enabled 

Setting Group 2: 

Disabled/Enabled 

Setting Group 3: 

Disabled/Enabled 

Setting Group 4: 

Disabled/Enabled 

System Config:   

Invisible/Visible 

Power:  

 

Disabled/Enabled 

Overcurrent:  

Disabled/Enabled 

Thermal Overload: 

Disabled/Enabled 

Earth Fault: 

 

Disabled/Enabled 

SEF/REF/Spower: 

Disabled or SEF/REF 

 

 

 

or Sensitive Power  

Residual O/V NVD: 

Disabled/Enabled 

df/dt:  

 

Disabled/Enabled 

V Vector Shift:   

Disabled/Enabled 

Reconnect Delay: 

Disabled/Enabled 

Volt Protection:  

Disabled/Enabled 

Freq Protection: 

Disabled/Enabled 

CB Fail: 

 

Disabled/Enabled 

Supervision:  

Disabled/Enabled 

Dynamic Rating  

Disabled/Enabled 

Input Labels:   

Invisible/Visible 

Output Labels:   

Invisible/Visible 

CT & VT Ratios: 

Invisible/Visible 

Event Recorder: 

Invisible/Visible 

Disturb Recorder: 

Invisible/Visible 

Measure’t Setup: 

Invisible/Visible 

Comms Settings: 

Invisible/Visible 

Commission Tests: 

Invisible/Visible 

Setting Values:  

Primary/Secondary 

Control Inputs:   

Invisible/Visible 

CLIO Inputs: 

 

Disabled/Enabled 

CLIO Outputs:   

Disabled/Enabled 

System Checks  

Disabled/Enabled 

Ctrl I/P Config:   

Invisible/Visible 

Ctrl I/P Labels:   

Invisible/Visible 

Direct Access:   

Disabled/Enabled 

IEC GOOSE 

 

Invisible/Visible 

RP1 Read Only  

Disabled/Enabled 

RP2 Read Only  

Disabled/Enabled 

NIC Read Only   

Disabled/Enabled 

LCD Contrast:   

0…31 

Содержание ALSTOM P341

Страница 1: ...AUTOMATION GRID MiCOM ALSTOM P341 Interconnection Protection Relay Software Version 36 71 Hardware Version J Technical Data Sheet P341 EN TDS F74...

Страница 2: ...d including settlements of warranties result solely from the applicable purchase contract which is not affected by the contents of the technical manual This device MUST NOT be modified If any modifica...

Страница 3: ......

Страница 4: ...0 0 12 3 12 3 4...

Страница 5: ......

Страница 6: ...00 01 1 2 33 1 3 30 30 4...

Страница 7: ...0 1 2 0 0 3 4 5 2 12 3 4 6 3 5 1 0 3 0...

Страница 8: ...0 10 2 0 13 4 2 1 2 3 5 6 6 7 8 8 7 6 9...

Страница 9: ...0 1 2 3 3 234 34 5 6 5 75 8 9...

Страница 10: ...01 21 3 1 4 56 1 0 31 0 31 0 31 7 8 6 9 1 2 3 31 121 7 9 8 6...

Страница 11: ...Isolation to ELV extra low voltage level Maximum cable length 15 m Front download monitor port EIA RS 232 25 pin D type female connector Socket SK2 For firmware and menu text downloads Isolation to EL...

Страница 12: ...cos unity AC 1500 VA inductive cos 0 5 Subject to maxima of 5 A and 250 V Ratings AC measuring inputs Nominal frequency 50 and 60 Hz settable Operating range 40 to 70 Hz AC current Nominal current In...

Страница 13: ...Battery backup Front panel mounted Type AA 3 6 V Lithium Thionyl Chloride Battery SAFT advanced battery reference LS14250 Battery life assuming relay energized for 90 time 10 years Field voltage outp...

Страница 14: ...ubject to the above limits of make break capacity rated voltage Make Carry Break 30 A for 3 secs dc resistive 5 000 operations subject to the above limits of make break capacity rated voltage 30 A for...

Страница 15: ...ommunications port terminals and protective earth conductor terminal ii Per ANSI IEEE C37 90 1989 reaffirmed 1994 1 5 kV rms AC for 1 minute across open contacts of normally open output relays 1 kV rm...

Страница 16: ...el 5 1000 A m applied in all planes Per IEC 61000 4 10 1993 Level 5 100 A m applied in all planes at 100 kHz 1 MHz with a burst duration of 2 s Conducted emissions Per EN 55022 1998 Class A 0 15 0 5 M...

Страница 17: ...ss 2 Endurance Class 2 Shock and bump Per IEC 60255 21 2 1996 Shock response Class 2 Shock withstand Class 1 Bump Class 1 Seismic test Per IEC 60255 21 3 1995 Class 2 P341 third party compliances Unde...

Страница 18: ...DT operation 2 or 50 ms whichever is greater DT Reset 5 Directional accuracy RCA 90 2 hysteresis 2 Characteristic UK IEC 6025 3 1998 Characteristic US IEEE C37 112 1996 Under reference conditions Nega...

Страница 19: ...time 60 ms 65 ms SEF Neutral displacement residual overvoltage Accuracy DT IDMT Pick up Setting 5 Drop off 0 95 x Setting 5 IDMT characteristic shape 5 or 55 ms whichever is greater DT operation 2 or...

Страница 20: ...ting 0 025 Hz 0 01 Hz DT operation 2 or 50 ms whichever is greater The operating will also include a time for the relay to frequency track 20 Hz second CB fail Timer accuracy Timers 2 or 40 ms whichev...

Страница 21: ...ty 1 CS2 CB Closing Timer Timer 30 ms Repeatability 10 ms System Split Accuracy SS Phase Angle Pick up Setting 2 1 Drop off Setting 1 1 Repeatability 1 SS Undervoltage Pick up Setting 3 Drop off 1 02...

Страница 22: ...tantaneous operating time 250 ms CLI DT operating time 2 setting or 200 ms whichever is the greater CLO conversion interval 5 ms CLO latency 1 07 s or 70 ms depending on CLO output parameter s interna...

Страница 23: ...22 5 23 5 20 3 14 dBm avg Optical Extinction Ratio 10 10 dB Output Optical Power at Logic 0 State PO 0 45 dBm avg BOL Beginning of life EOL End of life Receiver optical characteristics TA 0 C to 70 C...

Страница 24: ...ime Zone UTC Local Tunnel Time Zone UTC Local Configuration Setting Group Select via Menu Select via PSL Active Settings Group 1 2 3 4 Setting Group 1 Disabled Enabled Setting Group 2 Disabled Enabled...

Страница 25: ...rts trips controls logic Input 1 Trigger No Trigger Trigger LH Low to High Trigger H L High to Low up to Input 32 Trigger No Trigger Trigger L H Trigger H L Measured operating data measure t setup Def...

Страница 26: ...sabled Enabled Fault Freq Count 1 9999 Fault Freq Time 0 9999 s Opto coupled binary inputs opto config Global Nominal V 24 27 V 30 34 V 48 54 V 110 125 V 220 250 V Custom Opto Input 1 up to Opto Input...

Страница 27: ...0 V Equivalent range in Pn 0 5 157 Sen Power 1 Delay 0 00 100 0 s Power 1 DO Timer 0 00 100 0 s P1 Poledead Inh Disabled Enabled Comp angle C 5 5 0 Sen Power2 as Sen Power 1 Phase overcurrent overcurr...

Страница 28: ...20 x setting The IEC standard very and long time inverse curves become definite time at currents greater than 30 x setting For all IEC UK curves the reset characteristic is definite time only For all...

Страница 29: ...Curves Curve 5 100 0 10 0 1 0 Current Multiples of Is 0 1 1 10 100 Operating Time s Curve 6 Curve 9 Curve 7 Curve 8 P2137ENa NPS overcurrent 2 1 Status Disabled Enabled 2 1 Direction Non Directional D...

Страница 30: ...0 10 10 00 IN1 1 IDG Time 1 00 2 00 IN1 1 Reset Char DT Inverse IN1 1 tRESET 0 00 100 00 s IN1 2 as IN 1 IN1 3 Status Disabled Enabled IN1 3 Directional Non Directional Directional Fwd Directional Rev...

Страница 31: ...urrent elements stages 1 to 4 will be blocked if VTS detection of fuse failure occurs ISEF Char Angle 95 95 ISEF VNpol Set 0 5 80 0 V 100 120 V 2 320 V 380 480 V WATTMETRIC SEF PN Setting 0 20 In W 10...

Страница 32: ...5 V 100 120 V 240 740 V 380 480 V V 2 Time Delay 0 00 100 00 s The inverse characteristic is given by the following formula t K M 1 Where K Time multiplier setting t Operating time in seconds M Applie...

Страница 33: ...8 V 380 440 V CS Voltage Block None Undervoltage Overvoltage Differential UV O V UV Diff V OV Diff V UV OV Diff V Gen Underfreq 45 00 65 00 Hz Gen Overfreq 45 00 65 00 Hz Check sync CS1 Status Disable...

Страница 34: ...Wind Vel Corr 0 150 Wind Vel Min 0 00 60 00 m s Wind Vel Max 0 00 60 00 m s Wind Vel AvgSet Disabled Enabled Wind Vel Avg Dly 60 3600 s WV Input Type 0 1 mA 0 10 mA 0 20 mA 4 20 mA WV I P Minimum 0 0...

Страница 35: ...RMS 0 0 200 0 V Frequency 0 00 70 0 Hz 3 Phase Watts 6000 W 6000 W 3 Phase Vars 6000 Var 6000 Var 3 Phase VA 0 6000 VA 3Ph Power Factor 1 1 Single Phase Active Power A Phase Watts B Phase Watts C Phas...

Страница 36: ...ase VArs Phase VA All phase segregated power measurements real reactive and apparent A B C 3 Phase Watts 3 Phase VArs 3 Phase VA NPS Power S2 3Ph Power Factor Ph Power Factor Independent power factor...

Страница 37: ...l Data Sheet 35 P341 Software versions 36 71J Circuit breaker monitoring statistics CB Operations Total I Broken Cumulative breaker interruption duty on a per phase basis A B C CB Operate Time Reset C...

Страница 38: ...P341 Technical Data Sheet 36 P341 Software versions 36 71J CASE DIMENSIONS P1647ENd P341 case dimensions 40TE case P341 case dimensions 60TE case...

Страница 39: ...9 11 12 15 13 14 19 18 22 25 20 21 23 24 0V CONNECTED TX 1 2 NOT TO T7 COMMAND DO D7 ACKNOWLEDGE 10 16 EXTERNAL RESET DATA READY DATA 1 PORT KBUS EIA485 16 SCN 18 17 SINGLE PORT ETHERNET BOARD OR IRIG...

Страница 40: ...P341 Technical Data Sheet 38 P341 Software versions 36 71J Interconnection protection relay 40TE for embedded generation using VEE connected VT s 8 I P 7 O P...

Страница 41: ...P341 Technical Data Sheet 39 P341 Software versions 36 71J 10P34101_5 P4659ENa Interconnection protection relay 40TE for embedded generation and sensitive power 8 I P 7 O P...

Страница 42: ...P341 Technical Data Sheet 40 P341 Software versions 36 71J 10P34101_7 P4592ENb Interconnection protection relay 40TE for embedded generation and check synchronizing 8 I P 7 O P...

Страница 43: ...P341 Technical Data Sheet 41 P341 Software versions 36 71J Interconnection protection relay 40TE for embedded generation 8 I P 7 O P...

Страница 44: ...TYPE CASE EARTH MiCOM P341 PART OPTO 2 D4 48V DC FIELD VOLTAGE OUT AUX SUPPLY AC OR DC OPTO 7 OPTO 8 COMMON CONNECTION D17 D18 D14 D13 D15 D16 x V OPTO 3 OPTO 4 OPTO 5 OPTO 6 D11 D10 D12 D9 D8 D7 D5...

Страница 45: ...P341 Technical Data Sheet 43 P341 Software versions 36 71J Dynamic line rating protection relay 40TE 8 I P 7 O P CLIO...

Страница 46: ...P341 Technical Data Sheet 44 P341 Software versions 36 71J P2236ENa Interconnection protection relay 40TE for embedded generation 8 I P 15 O P...

Страница 47: ...P341 Technical Data Sheet 45 P341 Software versions 36 71J P2235ENa Interconnection protection relay 40TE for embedded generation 16 I P 7 O P...

Страница 48: ...P341 Technical Data Sheet 46 P341 Software versions 36 71J Interconnection protection relay 40TE for embedded generation 12 I P 11 O P...

Страница 49: ...P341 Technical Data Sheet 47 P341 Software versions 36 71J 10P34101_4 P4581ENa Dynamic line protection relay 60TE 16 I P 16 O P CLIO...

Страница 50: ...P341 Technical Data Sheet 48 P341 Software versions 36 71J 10P34106_1 P4579ENb Interconnection protection relay 60TE for embedded generation 24 I P 16 O P...

Страница 51: ...P341 Technical Data Sheet 49 P341 Software versions 36 71J P10P34107_1 P4580ENa Interconnection protection relay 60TE for embedded generation 16 I P 24 O P...

Страница 52: ...P341 Technical Data Sheet 50 P341 Software versions 36 71J 10P34111_1 P4582ENa Interconnection protection relay 60TE for embedded generation 16 I P 20 O P 4HB...

Страница 53: ...P341 Technical Data Sheet 51 P341 Software versions 36 71J 10P34112_1 P4583ENa Interconnection protection relay 60TE 16 I P 12 O P 4HB CLIO...

Страница 54: ...P341 Technical Data Sheet 52 P341 Software versions 36 71J GN0292_1 P4586ENa Assembly P341 interconnection and DLR protection relay 40TE 8 I P 7 O P with optional I P O P...

Страница 55: ...P341 Technical Data Sheet 53 P341 Software versions 36 71J P4656ENa GN0293_1 Assembly P341 interconnection and DLR protection relay 40TE 8 I P 7 O P with optional CLIO...

Страница 56: ...P341 Technical Data Sheet 54 P341 Software versions 36 71J P4655ENa GN0294_1 Assembly P341 interconnection and DLR protection relay 60TE 16 I P 16 O P with optional I P O P...

Страница 57: ...P341 Technical Data Sheet 55 P341 Software versions 36 71J P4654ENa GN0295_1 Assembly P341 interconnection and DLR protection relay 60TE 16 I P 16 O P with optional HB O P...

Страница 58: ...P341 Technical Data Sheet 56 P341 Software versions 36 71J P4653ENa GN0295_1 Assembly P341 interconnection and DLR protection relay 60TE 16 I P 16 O P with optional CLIO...

Страница 59: ...C Redundant Ethernet Self Healing Ring 2 multi mode fiber ports IRIG B Modulated G Redundant Ethernet Self Healing Ring 2 multi mode fiber ports IRIG B Unmodulated H Redundant Ethernet RSTP 2 multi mo...

Страница 60: ...0 5 C Software number Latest software 36 Latest software Dynamic Line Rating 71 Settings File Default Customer 0 A Design suffix Phase 2 CPU and front panel with 2 hotkeys and dual characteristic opto...

Страница 61: ......

Страница 62: ...Grid Substation Automation Solutions Business www alstom com grid Alstom Grid Worldwide Contact Centre online 24 hours a day 44 0 1785 250 070 www alstom com grid contactcentre PUBLICATION P341 EN TD...

Отзывы: