P341 Technical Data Sheet
32
P341 Software versions 36 & 71J
Fault Freq Lock:
Alarm disabled
Alarm enabled
Fault Freq Count: 1…9999
Fault Freq Time: 0…9999 s
Dynamic rating
Dyn Line Rating: Disabled/CIGRE Std 207/
IEEE Std 738
DLR LINE SETTING
Conductor Type: Gopher, Weasel, Ferret,
Rabbit, Horse, Dog, Wolf, Dingo, Lynx,
Caracal, Panther, Jaguar, Zebra, Fox, Mink,
Skunk, Beaver, Raccoon, Otter, Cat, Hare,
Hyena, Leopard, Tiger, Coyote, Lion, Bear,
Batang, Goat, Antelope, Sheep, Bison, Deer,
Camel, Elk, Moose, Custom
NonFerrous Layer: 1…3
DC Resist per km: 0.001…2.0000
Ω
Overall Diameter: 0.001…0.10000 m
Outer Layer Diam: 0.001…0.0100 m
TotalArea(mm sq): 10.00…1000.00 mm
2
TempCoefR x0.001: 1.00…10.00 K
mc: 1.0…5000.0 J/(m
⋅
K)
Solar Absopt: 0.23…0.95
Line Emissivity: 0.23...0.95
Line Elevation: -1000...6000 m
Line Azimuth Min: 0.0…360.0
°
Line Azimuth Max: 0.0…360.0
°
T Conductor Max: 0.0 …300.0
°
C
Ampacity Min: 0.100…4.000 In
Ampacity Max: 0.100…4.000 In
Drop-off Ratio: 70.0...99.0%
Line Direction: 0.0…360.0
°
DLR CHANNEL SET
Ambient Temp: Disabled, CLI1, CLI2, CLI3,
CLI4
Default Ambient T: -100.0 …100.0
°
C
Ambient T Corr: -50.0 …50.0
°
C
Ambient T Min: -100.0 …100.0
°
C
Ambient T Max: -100.0 …100.0
°
C
Ambient T AvgSet: Disabled/Enabled
Ambient T Avg Dly: 60…3600 s
Amb T Input Type : 0-1 mA, 0-10 mA,
0-20 mA, 4-20 mA
Amb T I/P Min: -100.0…100.0
°
C
Amb T I/P Max: -100.0 …100.0
°
C
Amb T I< Alarm: Disabled/Enabled
Amb T I< Alm Set: 0…4 mA
Wind Velocity: Disabled, CLI1, CLI2, CLI3,
CLI4
Default Wind Vel: 0.00…60.00 m/s
Wind Vel Corr: 0...150%
Wind Vel Min: 0.00…60.00 m/s
Wind Vel Max: 0.00…60.00 m/s
Wind Vel AvgSet: Disabled/Enabled
Wind Vel Avg Dly: 60…3600 s
WV Input Type : 0-1 mA, 0-10 mA, 0-20 mA,
4-20 mA
WV I/P Minimum: 0.00…60.00 m/s
WV I/P Maximum: 0.00…60.00 m/s
WV I< Alarm: Disabled/Enabled
WV I< Alarm Set: 0…4 mA
Wind Direction: Disabled, CLI1, CLI2, CLI3,
CLI4
Default Wind Dir: 0.0…360.0
°
Wind Dir Corr: -180.0…180.0
°
Wind Dir Min: 0.0…360.0
°
Wind Dir Max: 0.0…360.0
°
Wind Dirl AvgSet: Disabled/Enabled
Wind Dir Avg Dly: 60…3600 s
WD Input Type : 0-1 mA, 0-10 mA, 0-20 mA,
4-20 mA
WD I/P Minimum: 0.0…360.0
°
WD I/P Maximum: 0.0…360.0
°
WD I< Alarm: Disabled/Enabled
WD I< Alarm Set: 0…4 mA
Solar Radiation: Disabled, CLI1, CLI2, CLI3,
CLI4
Default Solar R: 0…3000 W
Solar Rad Corr: -1000...1000 W
Solar Rad Min: 0…3000 W
Solar Rad Max: 0…3000 W
Solar Rad AvgSet: Disabled/Enabled
Solar Rad Avg Dly: 60…3600 s
SR Input Type : 0-1 mA, 0-10 mA, 0-20 mA,
4-20 mA
SR I/P Minimum: 0…3000 W
SR I/P Maximum: 0…3000 W
SR I< Alarm: Disabled/Enabled
SR I< Alarm Set: 0…4 ma
DLR PROT
DLR I>1 Trip: Disabled/Enabled
DLT I>1 Set: 20.0%...200.0%
DLR I>1 Delay: 0…30000 s
DLR I>2/3/4/5/6 as DLR I>1
Input labels
Opto Input 1…32: Input L1…Input L32
Output labels
Relay 1…32: Output R1…Output R32
Current loop input
CLIO1 Input 1: Disabled/Enabled
CLI1 Input Type:
0 - 1 mA
0 - 10 mA
0 - 20 mA
4 - 20 mA
CLI1 Input Label: 16 characters (CLIO input 1)
CLI1 Minimum: -9999…+9999
CLI1 Maximum: -9999…+9999
CLI1 Alarm: Disabled/Enabled
CLI1 Alarm Fn: Over/Under
CLI1 Alarm Set: CLI1 min…CLI1 max
CLI1 Alarm Delay: 0.0…100.0 s
CLI1 Trip: Disabled/Enabled
CLI1 Trip Fn: Over/Under
CLI1 Trip Set: CLI1 min…CLI1 max
CLI1 Trip Delay: 0.0…100.0 s
Содержание ALSTOM P341
Страница 3: ......
Страница 4: ...0 0 12 3 12 3 4...
Страница 5: ......
Страница 6: ...00 01 1 2 33 1 3 30 30 4...
Страница 7: ...0 1 2 0 0 3 4 5 2 12 3 4 6 3 5 1 0 3 0...
Страница 8: ...0 10 2 0 13 4 2 1 2 3 5 6 6 7 8 8 7 6 9...
Страница 9: ...0 1 2 3 3 234 34 5 6 5 75 8 9...
Страница 10: ...01 21 3 1 4 56 1 0 31 0 31 0 31 7 8 6 9 1 2 3 31 121 7 9 8 6...
Страница 61: ......