2.3.5.1
WARNINGS ABOUT THE WATER CIRCUIT.
-
Set the water pressure in the boiler at least at 1,5 bar.
-
The water circulation in the boiler must be always guaranteed by means of a pump;
THIS PUMP HAS TO BE PLACED ON THE RETURN, otherwise you can have risks of
overheating and calcareous scaling problems. The water flow rate in the boiler must ensure a flow-
return
∆
T between 5K and 30K. This is valid particularly for each boiler of a cascade installation.
-
Dirty in water can cause serious problem to the boiler structure, because such material can close
the water distributor holes, than an over-temperature in top of the boiler can occur. So, make sure
that the circuit water is clean, if necessary by means of adequate filters or vertical LOW LOSS
HEADER. This second solution allows also to separate the boiler circuit from the uses circuit.
-
In the case of installations in known hard water areas (hardness greater than 20 French
degrees) or in an heating system were leakages are suspected, appropriate treatment of the
system fill water is REQUIRED.
L1
D1
D3
D2
D4
L1
L2
D2
L2
H
D1
H
3/4"F
x
20
1/2"Fx 20
3/4"M
1/2"Fx 20
3/4"F
x
20
1/2"Fx 20
3/4"M
1/2"Fx 20
D5
D5
-
If, possible, install the right-settled pressure safety valve following the system calculation on the
tube provided with the purging valves at the top of the rear section
-
If there is a need to treat the water with an anti-freeze agent, then carefully follow the
recommendations of the anti-freeze supplier/manufacturer, especially when mixing water with the
antifreeze.
2.3.6
GAS CONNECTION
Suitably qualified and competent personnel should carry out the gas train installation.
The gas connection should comply with relevant requirements of Gas Safety (Installation and Use)
Regulations.
Always include a manually operated shut-of/valve in the gas train when carrying out the installation.
This is required to isolate the burner for maintenance and servicing requirements, or for when the
burner is taken out of use for prolonged periods.
Before commencing the installations ensure that the gas supply is turned off and that all electrical
supplies to the burner are also disconnected.
Gas supply pipework should be fitted in accordance with CP.331/3, taking into account the size of the
boiler (see technical data § 1.4).
2.3.7
FLUE CONNECTION
The boiler should be connected to the a natural draught chimney with rigid flue pipes and fittings,
constructed and dimensioned according to the Local Regulations in force.