Operating Instruction MHM Flash Cures
Operating instructions MHM Flash Cures.docx
Page 13 of 17
7.2.
Overheat protection
When the temperature inside the unit rises above 70 °Celsius, the unit switches off automatically to
protect the electronics. In this case, the temperature inside the controller will be shown in the
‘POWER/TEMP1’ display. While the unit cools down, make sure that the fans are working and the
cover grill is not obstructed. Should the unit require cleaning, switch off and unplug the power cord.
When the unit has cooled down it may be restarted using the ‘TEST’ switch, which will return the
unit to the standby position.
7.3.
Programming the Flash Cure
The unit as delivered has the normal standby and maximum heat output levels as well as a low
standby level and the time before this low level is activated pre-set.
The user may change any or all of these settings as follows:
Press and hold ‘FUNCTION’ button until display changes - approximately 5 seconds.
This set up program may be interrupted and the unit returned to normal operating mode at any time
by pressing the ‘TEST’ button.
The manufacturer’s settings are:
[S-d] [000]
[P-H] [099]
[P-L] [020]
[P-d] [003]
[d-d] [002]
As soon as an input signal is received the unit will operate normally irrespective of whether it is in
the normal or low level standby position.
While the unit is in the low level standby position the displays will display [PPP] and [ddd].
Do not cover or obstruct the fans. This may result in loss of efficiency or reduction
of lifetime.
Do not touch the lamps or reflector while the unit is in use or before it has cooled
down after switching off.
To switch off the low level standby setting the [d-d] time should be set to [000].