ThermSelect®
5. Technical Data
21/100
Erection measurements and dimensions, split evaporator for ThermSelect
®
Fig. 3:
Erection measurements and dimensions, split evaporator for ThermSelect
®
Legend for Fig. 3:
Abbreviation
Meaning
ThermSelect
®
...
15
19
28
34
41
1
Fluid line
15
18
22
2
Suction gas line
28
35
42
3
Hot-gas thawing
12
15
18
A
Weather guard in mm
2155
3080
B
Floor mount in mm
1880
2805
C
Min. distance to walls and obstacles
> 200 mm
D
Min. distance to walls and obstacles
> 500 mm
EAL
Electrical connection of fan (split evaporator)
3x0.75 mm²
supply line 0-10 V signal 2x0.75 mm²
FA
Foundation
Take note of the following information!
KB
Gravel bed
min. 250 mm deep
KRS
Refrigerant pipe connection
STR
Direction of flow
ZAF
Supply line temperature sensor
2x2x0.75 mm²
(see also page 34 "Electrotechnical data controller")
NOTE!
It Fig. 3 represents a schematic diagram. It is not to be used instead of a professional layout de-
signed by professionals.
The foundation and the gravel bed must reach at least across a width of 400 mm.
The gravel bed must reach up to approx. to the foundation.
Содержание ThermSelect
Страница 1: ...ThermSelect As of 9 March 2011...
Страница 22: ...5 Technical Data ThermSelect 22 100 5 2 Identification plate Fig 4 Sample identification plate...
Страница 25: ...ThermSelect 5 Technical Data 25 100...
Страница 31: ...ThermSelect 5 Technical Data 31 100...
Страница 45: ...ThermSelect 6 Assembly 45 100 Fig 10 Sensor cable heat source inlet 5...
Страница 72: ...8 Maintenance ThermSelect 72 100 8 4 Spare part drawing and legend Fig 37...
Страница 96: ...Your notes ThermSelect 96 100...
Страница 97: ...ThermSelect Your Notes 97 100...
Страница 98: ...Your notes ThermSelect 98 100 12 Index...
Страница 100: ...Your notes ThermSelect 100 100...