ThermSelect®
6. Assembly
43/100
CAUTION!
Device damage through dirt and humidity.
Dirt and humidity can enter the pipes when installing
them.
Therefore:
-
Make sure that no dirt or humidity enters the pipes
while installing them.
-
When laying pipelines underground, the laying
depth must be a minimum of 25 cm (on passable
routes, a minimum of 50 cm).
-
The installation of the pipelines must be carried out
using a protective DN 100 pipe.
-
The ends of the protective pipe must be sealed and
waterproofed.
-
The wall duct must be watertight.
-
Do not let clipping particles get into the refrigerant
line as these cause the destruction of the compres-
sor.
NOTE!
The heating pump contains refrigerant for a 15m
max. length cooling line.
Any shortening or lengthening of the line may only
be carried out by a certified technician. The refrige-
rant dosage must be checked for line lengths exceed-
ing 20m, and be adjusted where required (approx.
dosage values are available in chap. 5.3).
NOTE!
The split evaporator contains a protective gas (nitro-
gen) and must be evacuated simultaneously with the
refrigerant lines.
NOTE!
The technician must check the installation and
mountings of the pipe, and establish a proper con-
nection with the heating pump and the split evapora-
tor.
NOTE!
Ball valves must remain shut (delivery condition)!
Содержание ThermSelect
Страница 1: ...ThermSelect As of 9 March 2011...
Страница 22: ...5 Technical Data ThermSelect 22 100 5 2 Identification plate Fig 4 Sample identification plate...
Страница 25: ...ThermSelect 5 Technical Data 25 100...
Страница 31: ...ThermSelect 5 Technical Data 31 100...
Страница 45: ...ThermSelect 6 Assembly 45 100 Fig 10 Sensor cable heat source inlet 5...
Страница 72: ...8 Maintenance ThermSelect 72 100 8 4 Spare part drawing and legend Fig 37...
Страница 96: ...Your notes ThermSelect 96 100...
Страница 97: ...ThermSelect Your Notes 97 100...
Страница 98: ...Your notes ThermSelect 98 100 12 Index...
Страница 100: ...Your notes ThermSelect 100 100...