Relay output QX3
Off, On
Off
9034
Relay output QX4
Off, On
Off
9050
Relay output QX21
module 1
Off, On
Off
9051
Relay output QX22
module 1
Off, On
Off
9052
Relay output QX23
module 1
Off, On
Off
9053
Relay output QX21
module 2
Off, On
Off
9054
Relay output QX22
module 2
Off, On
Off
9055
Relay output QX23
module 2
Off, On
Off
9056
Relay output QX21
module 3
Off, On
Off
9057
Relay output QX22
module 3
Off, On
Off
9058
Relay output QX23
module 3
Off, On
Off
Burner Control
9500
Pre-purge time
0
– 51
10
S
9501
Pre-purge time min
0
– 51
10
S
9504
Required speed pre-
purging
200
– 10000
2400
Min
-1
9505
Req. speed pre-
purging min
200
– 10000
2400
Min
-1
9506
Speed tolerance pre-
purging
50
– 1200
600
Min
-1
9512
Required speed
ignition
200
– 10000
2700
Min
-1
9513
Required speed
ignition max
200
– 10000
2700
Min
-1
9514
Speed tolerance
ignition
50
– 1200
600
Min
-1
9517
Pre-ignition time
0.4
– 1200
1
S
9518
Safety time
1.8
– 9.8
5
S
9519
Safety time with
ignition
0.2
– 9.6
4.6
S
9524
Required speed LF
0
– 10000
1250
Min
-1
9525
Required speed LF
min
0
– 10000
1250
Min
-1
9526
Required tolerance LF
50
– 1200
600
Min
-1
9529
Required speed HF
0
– 10000
60000
Min
-1
9530
Required speed HF
max
0
– 10000
60000
Min
-1
9531
Required tolerance HF
50
– 1200
600
Min
-1
9534
Optg time with ignition
load
0.2
– 10
1
S
9540
Post-purge time
0
– 51
5
S