Floor curing setp.
manually
0
– 95
25
°C
1155
Floor curing setp.
current
0
– 95
°C
1156
Floor curing day
current
0
– 32
°C
1161
Excess heat draw
Off, Heating mode, Always
Always
1170
With buffer
No, Yes
Yes
-
1172
With prim
contr./system pump
No, Yes
Yes
1180
Pump speed reduction
According HC operating level,
According characteristic curve,
Temp. differential nominal
According
characteristic
curve
1181
Starting speed
0
– 100
100
%
1182
Pump speed min
P1185
– P1183
50
%
1183
Pump speed max
P1182
– P1186
100
%
1185
Pump speed min OEM
0
– P1182
50
%
1186
Pump speed max
OEM
P1183
– 100
100
%
1188
Curve readj. at 50%
speed
0
– 100
33
%
1189
Filter time const.
speed ctrl.
0
– 20
5
Min.
1190
Flow setp. readj.
speed ctrl.
No, Yes
No
1198
Operating level
changeover
Frost protection, Reduced, Comfort
Reduced
1200
Optg mode
changeover
None, Protection, Reduced, Comfort,
Automatic
Protection
Heating Circuit 3
1300
Operating Mode HC3
Protection, Automatic, Reduced,
Comfort
Automatic
-
1310
Comfort Setpoint
P1312
– P1316
20.0
°C
1312
Reduced Setpoint
P1314
– P1310
16.0
°C
1314
Frost Protection
Setpoint
4
– P1312
10.0
°C
1316
Comfort Setpoint Max
P1310 - 35
35.0
°C
1320
Heating Curve Slope
0.10 - 4.00
1.50
3.20
-
1321
Heating Curve
Displacement
-4.5 - 4.5
0.0
°C
1326
Heating Curve
Adaption
Off - On
Off
-
1330
Summer/Winter
heating limit
---/8
– 30
18
°C
1332
24-Hour heating limit
---/-10
– 10
-3
°C
1333
Ext’n 24-Hour heating
limit
Yes
– No
Yes
1340
Flow temp setpoint
min
8
– P1341
8
°C
1341
Flow temp setpoint
max
P1340
– 95
85
°C