With prim.
Contr./system pump
No, Yes
Yes
Consumer Circuit 2
1909
Flow temp. setp. cons.
request
8
– 120
70
°C
1924
DHW charging priority
Yes, No
Yes
1925
Excess heat draw
Off, On
On
1928
With Buffer
No, Yes
Yes
1930
With prim.
Contr./system pump
No, Yes
Yes
Swimming pool Circuit
1959
Flow temp. setp. cons.
request
8
– 120
70
°C
1947
DHW charging priority
Yes, No
Yes
1945
Excess heat draw
Off, On
On
1948
With Buffer
No, Yes
Yes
1980
With prim.
Contr./system pump
No, Yes
Yes
Swimming pool
2055
Setpoint solar heating
8
– 80
26
°C
2056
Setpoint source
heating
8
– 80
22
°C
2065
Charging priority solar
Priority 1, Priority 2, Priority 3
Priority 3
2070
Swimming pool temp
max
P2055
– 95
32
°C
2080
With solar integration
No, Yes
Yes
Primary contr./system pump
2110
Flow temp. setpoint
min
8
– P2111
8
°C
2111
Flow temp. setpoint
max
P2110
– 95
80
°C
2121
Syst. Pump on heat
gen. lock
Off, On
Off
2130
Mixing valve boost
0
– 50
10
°C
2132
Actuator type
Two position, Three position
Three position
2133
Switching differential
2-pos.
0
– 20
2
°C
2134
Actuator running time
30
– 873
120
S
2135
Mixing valve Xp
1
– 100
32
°C
2136
Mixing valve Tn
10
– 873
120
S
2150
Primary contr./system
pump
Up stream of buffer, Downstream
from buffer
Downstream from
buffer
-
Boiler
2203
Release below outside
temp.
---/-50
– 50
0
°C
2208
Full charging buffer
Off, On
Off
2210
Setpoint min
P2211
– P2214
10
°C
2211
Setpoint min OEM
8
– P2210
40
°C
2212
Setpoint max
P2214
– P2213
90
°C
2213
Setpoint max OEM
P2212
– 120
85
°C