Cooling circuit 1
Line no.
Data point
Value
Unit
901
Operating mode
cooling circuit 1
Automatic
902
Room temp Comfort
setpoint cooling
circuit 1
24 °C
907
Release cooling
circuit 1
24h/day
908
Flow setpoint at
outside temp 25°C
CC1
20 °C
909
Flow setpoint at
outside temp 35°C
CC1
16 °C
912
Cooling limit at outs
temp cooling circuit 1
20 °C
913
Remaining time after
heating cooling
circuit 1
24 h
918
Start summer
compensation at
ouside temp CC1
26 °C
919
End summer
compensation at
ouside temp CC1
35 °C
920
Summer
compensation
setpoint increase CC1
4 °C
923
Flow setpoint min at
outside temp 25°C
CC1
18 °C
924
Flow setpoint min at
outside temp 35°C
CC1
18 °C
928
Room temperature
gain factor cooling
circuit 1
80 %
932
Room temp
limitation cooling
circuit 1
0.5 °C
938
Mixing valve decrease
cooling circuit 1
0 °C
939
Actuator control
mode cooling circuit
1
Three-position
940
Actuator switching
diff cooling circuit 1
2 °C
941
Running time
actuator cooling
circuit 1
120 s
942
P-band (Xp) cooling
circuit 1
12 °C
943
Integral action time
(Tn) cooling circuit 1
90 s