22.0 HM Appliances and Slave units equipped with OCI420 Communication Clips.
Communication Operation Indications
The RED LED on the OCI420 communication clip mounted on the front of each LMU64 module controller
flashes to indicate the detected operational status of the module dictated by the LPB communication from
the RVS43 Cascade Manager.
LED FLASH STATUS
INTERPRETATION OPTIONS
LED ON Constantly
OCI420 not configured to operate with LMU64
LED OFF Constantly
OCI420 Configured. LPB Short Circuit / No Power.
LED ON 93% OFF 7%
OCI420 and LUM64 Not Compatible / LPB Address inadmissible.
LED ON 5% OFF 95%
Boiler being controlled via LPB and required to be not
operating.
LED ON 5% OFF 20% ON 5% OFF 70%
Boiler being controlled via LPB and required to be operating.