9.0 BMS Interface Clip Installation and Parameter Alteration
Following the installation of the AGU2.511 communication clip (complete with base mounted wiring
connection) onto the front of the LMU64 controller a number of operational parameters within the
unit must be altered to ensure the clips operates as required.
LMU64 Pictured above with AGU2.511 and OCI420 communication clips.
A number of parameters will require altering within the LMU64 controller from their standard default setting to
allow the AGU2.511 communication clip to operate correctly.
Access is gained to the H parameters by pressing the PROG
buttons simultaneously for 3 seconds unit H
90 appears on the screen. The required H parameters can then be reached by using the PROG
or
buttons.
Once at the required H parameter the required setting is achieved by using the
buttons.
To save the alteration in the controller the INFO button must be pressed.
Parameter #
Description
Default
New Setting
Programmable Inputs
H618
Input control configuration
Input value interpretation affected by H622 or H623 Dependant
upon control requirement.
(4 is recommended.)
0
4. Predefined Temperature set point
5. Predefined Boiler Output
6. Low Loss Header Sensor
H622
Maximum Temperature Via X51 input 0-10 Volt
When H618 is set to 4
85 85
H623
Percentage level reached by input prior to boiler activation.
When H618 is set to 5
5 5
Programmable Outputs
H619
Relay designation for Output from Orange Plug
Left Terminal Live.
Right Terminal Neutral.
Output rated at 240 Volts 0.5 Amp
3
0. Hydraulic Diagram Derived.
1. LPG SSOV Output.
2. Boiler Fault Output.
3. Boiler Operating Output.
4 -12 Non Supported Output.
H620
Relay designation for Output from Clear Plug
Left Terminal Live.
Middle Terminal Neutral.
Output rated at 240 Volts 0.5 Amp
2
0. Hydraulic Diagram Derived.
1. LPG SSOV Output.
2. Boiler Fault Output.
3. Boiler Operating Output.
4 -12 Non Supported Output.
H621
Relay designation for Output from Clear Plug
Right Terminal Live.
Output rated at 240 Volts 0.5 Amp
0
0. Hydraulic Diagram Derived.
1. LPG SSOV Output.
2. Boiler Fault Output.
3. Boiler Operating Output.
4 -12 Non Supported Output.