3. Operations 

 

System Administration 

Creating a location description 

The Set Location command specifies text that appears in the HTML control screen’s Location field. The text is 
also appended to a Welcome to banner that appears when a user successfully logs in serially or through a 
Telnet session. 

If you do not issue this command, or if you issue this command without specifying any text, the control screen ’s 
Location field will be blank and no Welcome to banner will be displayed. 

To create a location description: 

At the Switched PDU: prompt, type 

set location

, followed by a descriptive name of up to 24 alphanumeric and 

other typeable characters (ASCII 32 to 126 decimal - spaces are allowed). Press 

Enter

Omitting any characters after typing ‘set location’ deletes any previously specified text. 

Examples 

The following command specifies Florida HQ as the descriptive location for the control screen and the login 
banner: 

Switched PDU: set location Florida HQ<Enter> 

The following command deletes any previously specified location description: 

Switched PDU: set location<Enter> 

In this case, the control screen’s Location field will be blank, and no welcome banner will be displayed after a 
successful login. 

Displaying system configuration information 

The Show System command displays all system configuration information.  

 Firmware 

version 

 

NIC module serial number and MAC address 

 

Hardware revision code and Flash size 

 

Uptime since last system restart 

 

System location description 

To display system configuration information: 

At the Switched PDU: prompt, type 

show system

 and press 

Enter

Example 

   System Information 
      F/W Version:   Switched PDU Version 5.3a 
      NIC S/N:       1600001 
      MAC Address:   00-0a-9c-10-00-01 
      H/W Rev Code:  0 
      Flash Size:    1 MB 
      Uptime:        0 days 6 hours 14 minutes 1 second 
      Location:      Florida HQ 

301-0399-4 Rev A. - Page 37 

Содержание Switched PDU

Страница 1: ...www mgeups com Switched PDU T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R Installation and user manual...

Страница 2: ...stems peritoneal dialysis systems neonatal ventilator incubators ventilators for adults or infants anesthesia ventilators infusion pumps and any other devices designated as critical by the U S FDA Com...

Страница 3: ...Power Input Retention Bracket 7 Mounting 8 Attaching the Expansion Module 8 Connecting to the Power Source 8 Connecting Devices 9 Connecting to the Unit 9 OPERATIONS 12 Interfaces 12 HTML Interface 1...

Страница 4: ...nt to your network 1 Mount the Switched PDU 7 2 Connect to the power source 8 3 Connect the devices to the Switched PDU 9 4 Connect to the Switched PDU 9 5 Configure the Switched PDU 9 Login as the pr...

Страница 5: ...sets of screws and washers Horizontal Rack two mounting L brackets and four screws RJ45 to RJ45 crossover cable DB9F to DB25M modem cable RJ45 to DB9F serial port adapter for connection to standard D...

Страница 6: ...or 1 LN K 16 15 14 13 12 11 10 9 9 16 1 8 Inpu t Cur rent CAUTION To pr ev en t fire replac e with sa me size an d type fuse on ly Alw ay s disc on ne ct the po wer su pp ly co rd be fo re op en ing...

Страница 7: ...cherungsschutz versehen sein Ein Switched PDU verf gt ber keinen Hauptschutzschalter bzw ber keine Sicherung damit kein einzelner Fehlerpunkt entstehen kann Der Kunde ist daf r verantwortlich den Stro...

Страница 8: ...about 1 inches of vertical adaptability 3 Attach the top and bottom brackets to your rack Attac C nsion Module with the prov hing the Expansion Module onnect the Switched PDU Expa ided RJ12 crossover...

Страница 9: ...den Aufmachen um elektrischen Schlag zu vermeiden Connecting the Sensors The Switched PDU is equipped with two mini RJ11 T H ports for attachment of the included Temperature Humidity sensor Attach th...

Страница 10: ......

Страница 11: ...lnet SSH 16 HTTP SSL 16 Serial Ports 17 Outlets 18 Groups 18 Users 18 FTP 19 SNTP 20 SNMP 20 Tools 21 Restart 21 COMMAND LINE INTERFACE 21 Logging In 21 Operations Commands 24 Administration Commands...

Страница 12: ...Switched PDU has one predefined administrative user account username password admn admn and supports a maximum of 128 defined user accounts NOTE For security MGE UPS SYSTEMS recommends removal of the...

Страница 13: ...data and allow changes to outlet states or system configuration The following sections describe each interface section page and their use Log Figure 4 Example HTML page ging In Logging in through HTM...

Страница 14: ...Apply Group The Group outlet control page displays all groups assigned to the current user as well as the outlets for each group To select a group Select the group name from the drop down menu and pr...

Страница 15: ...names up to 24 alphanumeric and other typeable characters ASCII 33 to 126 decimal spaces and colon characters are not allowed are allowed NOTE Spaces may be used for the location description only Cre...

Страница 16: ...e IP address subnet mask or gateway In the appropriate field enter the IP address subnet mask or gateway address and press Apply Telnet SSH The Telnet SSH configuration page used to enable or disable...

Страница 17: ...1 0 Select Basic or MD5 from the Authentication drop down menu and press Apply Setting SSL access level Switched PDU SSL supports configuration of SSL connections as being either optional or required...

Страница 18: ...the group to be removed and press Yes on the subsequent confirmation window Adding and Deleting outlets from a group Press the Edit link in the Action column for the associated group On the subsequen...

Страница 19: ...he associated user On the subsequent User Edit page select Yes or No from the Environmental Monitoring drop down menu and press Apply Adding and Deleting outlet access Click on the Outlets link in the...

Страница 20: ...suppressed until the Tower Status returns to Normal Enabling or disabling SNMP support Select Enabled or Disabled from the drop down menu and press Apply Setting the community strings Enter the commu...

Страница 21: ...a supported data rate 300 1200 2400 4800 9600 19200 38400 57600 or 115200 BPS 8 data bits no parity one stop bit and Device Ready output signal DTR or DSR To log in by RS 232 or Telnet 1 Press Enter T...

Страница 22: ...s a user access to one or more groups Add Outlettogroup Adds an outlet to a group name Add Outlettouser Grants a user access to one or all outlets Add Porttouser Grants a user access to one or all ser...

Страница 23: ...a descriptive field for the Switched PDU Set User Access Sets the access level for a user Set User Envmon Grants or removes privileges to view input and environmental monitoring status Set User Passwo...

Страница 24: ...s will be displayed To turn outlets off At the Switched PDU prompt type off followed an outlet and press Enter or Type off followed by a group name and press Enter or Type off all and press Enter Exam...

Страница 25: ...Switched PDU prompt type status followed by an outlet name and press Enter or Type status followed by a group name and press Enter or Type status and press Enter Examples The following command displa...

Страница 26: ...groups for the current user To display accessible groups At the Switched PDU prompt type list groups and press Enter Example The follow command displays all accessible groups for the current user Swit...

Страница 27: ...absolute and descriptive names and the Input Status and current Load reported to the Switched PDU by the infeed To display status of one or more infeeds Type istat and press Enter or Type iload and pr...

Страница 28: ...mental Monitor A Name Florida_HQ_1 Status Normal Temperature Humidity Sensors ID Name Temperature Humidity A1 Temp_Humid_Sensor_A1 Not Found Not Found A2 T H2_Florida_HQ_1 23 5 Deg C 22 RH Starting a...

Страница 29: ...type a password of up to 16 alphanumeric and other typeable characters ASCII 32 to 126 decimal Passwords are case sensitive Press Enter To specify no password press Enter at the prompt At the Verify...

Страница 30: ...r Password Enter Verify Password Enter Setting user access level privileges The Set User Access command sets the access level privileges for a user The Switched PDU has four defined access privilege l...

Страница 31: ...access privilege level To display user access privilege levels At the Switched PDU prompt type list users and press Enter Example The following command displays all users with their access privilege l...

Страница 32: ...Group_1 and ServerGroup_2 Switched PDU add GroupToUser ServerGroup_1 janedoe Enter Switched PDU add GroupToUser ServerGroup_2 janedoe Enter Deleting group access for a user The Delete GroupFromUser co...

Страница 33: ...et A2 which has a descriptive name of WebServer_1 group ServerGroup_1 group ServerGroup_2 and Console serial port Group Administration Creating a group name The Create Group command creates a new grou...

Страница 34: ...Group Enter Outletname all Enter Groupname ServerGroup_1 Enter Deleting an outlet from a group The Delete OutletFromGroup command deletes an outlet from a group To delete more than one outlet but not...

Страница 35: ...outlet name Press Enter Example The following command sets the wakeup state for outlet a1 to off Switched PDU set outlet wakeup off a1 Enter Displaying outlet information The Show Outlets command dis...

Страница 36: ...the Switched PDU prompt type set port speed follow by the data rate and press Enter Example The following command sets the serial ports data rate to 38400 BPS Switched PDU set port speed 38400 Enter...

Страница 37: ...he following command specifies Florida HQ as the descriptive location for the control screen and the login banner Switched PDU set location Florida HQ Enter The following command deletes any previousl...

Страница 38: ...press Enter Example Switched PDU show towers Enter Tower Tower ID Name A Florida_HQ_1 Creating a descriptive infeed name The Set Infeed Name command assigns a descriptive name to an infeed This descri...

Страница 39: ...the IP address At the Switched PDU prompt type set ipaddress followed by the IP address and press Enter Example The following command sets the IP address to 12 34 56 78 Switched PDU set ipaddress 12 3...

Страница 40: ...rt 80 Security BASIC SSL Enabled Access Required SNMP Enabled Network Status Link Up Speed 100 Mbps Duplex Full Negotiation Auto HTTP Administration NOTE A restart is required after setting or changin...

Страница 41: ...mmand To change the Telnet socket At the Switched PDU prompt type set telnet port followed by the port number and press Enter Example The following changes the Telnet port number to 7001 Switched PDU...

Страница 42: ...the filepath for the file to be uploaded The FTP Filepath command sets the filepath for the firmware file to be uploaded To set the FTP filepath At the Switched PDU prompt type set ftp filepath follo...

Страница 43: ...Enter Example The following command set the primary SNTP server address to 204 152 184 72 Switched PDU set sntp primary 204 152 184 72 Enter Displaying SNTP configuration information The Show SNTP com...

Страница 44: ...5 SSL Technical Specifications 45 SSH 46 Enabling and Setting up SSH Support 46 SSH Technical Specifications 46 SNMP 47 MIB OID and Support Error Bookmark not defined Enabling and Setting up SNMP Supp...

Страница 45: ...disables SSL support Set SSL access Sets SSL access as optional or required Enabling and Setting up SSL Support NOTE A restart of the Switched PDU is required after setting or changing ANY SSL configu...

Страница 46: ...SSH Support NOTE A restart of the Switched PDU is required after setting or changing ANY SSH configurations See Performing a warm boot on page 39 for more information Enabling or disabling SSH suppor...

Страница 47: ...set community string Set snmp trapdest1 Sets a destination IP addresses for traps Set snmp trapdest2 Sets a destination IP addresses for traps Set snmp traptime Sets the delay for steady state condit...

Страница 48: ...timer period to 180 seconds Switched PDU set traptime 180 Enter Setting the Get Set community strings Switched PDU supports two SNMP community strings that provide varying levels of access to objects...

Страница 49: ...I O Operational status change Change O Control status change Load I Input load out of limit All traps include the Location of the Switched PDU as defined with the Set Location command See Creating a l...

Страница 50: ...ap is generated Infeed and Outlet Status traps are suppressed until the Tower Status returns to Normal Change trap The Change trap is generated for all outlet status changes between any on off conditi...

Страница 51: ...nsor has been lost NoComm x Communication to the sensor has been lost Humidity Trap The Humidity trap is generated whenever the umidity on a temperature humidity sensor is beyond preset thresholds Hum...

Страница 52: ...bles or disables the Outlet Status trap Show Traps Displays trap configurations Enabling or Disabling a Status trap The Set Trap Status command is used to enable or disable Status traps for a Tower In...

Страница 53: ...loadhigh followed by the infeed name and a value from 0 to 255 in amperes Press Enter Example The following command sets the infeed load limit for the second infeed on the first tower to 25 amperes us...

Страница 54: ...Humid trap To Enable or Disable the Humid trap At the Switched PDU prompt type set trap ths humid followed by the sensor name and on or off Press Enter Example The following command enables the Humid...

Страница 55: ...A BA HQ_2_Infeed_A ON ON 255 A More Y es N o y Outlet trap configuration Outlet Outlet Change Status ID Name Trap Trap AA1 DataServer_1 OFF ON AA2 WebServer_1 OFF ON AA3 FileServer_1 OFF ON AA4 OFF O...

Страница 56: ...t to factory defaults using the reset button 57 UPLOADING FIRMWARE 57 To initiate an FTP upload session from the HTML interface 57 To initiate an FTP upload session from the command line 57 TECHNICAL...

Страница 57: ...ast ten seconds NOTE If the reset button is depressed and held for more than 15 seconds the reset will abort Uploading Firmware You may upload new versions of firmware using File Transfer Protocol FTP...

Страница 58: ...et selected at time of purchase Power Ratings Input Current Ratings1 Output Current Ratings L indice du courant d entr e L indice du courant de sortie Eingangsstromst rke Ausgangsstromst rke Model Vol...

Страница 59: ...ver cable Pin DCE Signal Name Input Output 1 2 Receive Data RD Output 1 2 3 4 5 6 7 8 9 3 Transmit Data TD Input 4 Data Terminal Ready DTR Input 5 Signal Ground 6 Data Set Ready DSR Output 7 Request t...

Страница 60: ......

Страница 61: ......

Страница 62: ......

Отзывы: