The extended battery cabinet installation to the EXL 1000
UPS should be performed by a trained electrician. If the UPS
is already connected to utility, power down the UPS by
shutting off the upstream circuit breaker and shutting off the
battery circuit breaker on the UPS. Wait at least 5 minutes
before installing extended battery cabinet to UPS.

There are landings on both the UPS and the extended
battery cabinet for 3/4 inch flexible conduit, which should be
used to house cable wiring. All wire gauges and installation
should be performed as per local and NEC codes.

EXL 1000 UPS output 208 or 240 VAC phase to phase.
There is no neutral.  Battery terminal blocks, located at rear
panel of UPS, are provided on the back of the UPS for
connection of one or more external battery cabinets. The
smaller terminal blocks are for connection of a customer
supplied EPO circuit. 

Connect 3/4 inch flexible conduit of appropriate length and
slack, as per local and NEC code, to the conduit landings of
the EXL 1000 UPS and the extended battery cabinet. Using
the rightmost hole on the UPS landing and the leftmost
landing on the extended battery cabinet will allow for the
most direct path for wires. Secure the conduit to the landings
with flexible metal conduit fittings.

Position battery cabinet near EXL 1000 series UPS. Set
leveling feet on battery cabinet to stabilize unit.

If UPS is already installed and supplying power to a load,
place in “MAINTENANCE BYPASS” before continuing instal-
lation by doing the following:

Go to front of UPS and press gray button. This turns off
the UPS inverter and automatically transfers the UPS
output to static bypass that continues to power the load.

Go to rear of UPS and turn maintenance bypass switch
to the BYPASS position.

Turn off the battery circuit breaker on the UPS and the
battery cabinet.

Remove conduit landing covers from UPS and battery
cabinet by using a torx screw driver to remove torx screws
that fasten conduit landing covers. (see figure 1-2)

1.3.1

Electrical

Installation of

Battery Cabinet

1.3

Wiring connections

86-153226-01

1 — 3

Installation manual

Содержание EXL 1000

Страница 1: ...EXL 1000 Extended Battery Cabinet Installation Manual...

Страница 2: ...nergy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio commu nications Operation of this equipment in a residential area is likely to cau...

Страница 3: ...86 153226 01 B00 11 97 Copyright 1997 MGE UPS Systems Inc All rights reserved Printed in U S A MGE UPS Systems 1660 Scenic Avenue Costa Mesa CA 92626 714 557 1636 86 153226 01 EXL 1000 Extended Batte...

Страница 4: ...by others carry any warranty the manufacturers have made to MGE UPS Systems Inc and which can be passed on to Purchaser MGE UPS Systems Inc makes no warranty with respect to whether the products sold...

Страница 5: ...lts holding Extended battery cabinet to shipping base and EXL 1000 ramp for lowering 1 2 1 2 Maintenance Bypass Switches 1 4 1 3 Preparing the conduit wire prior to connecting the UPS Landing 1 5 1 4...

Страница 6: ...PORTANT notebox indicates information provided as an operating instruction or as an operating tip CAUTION A CAUTION notebox indicates information provided to protect the user and service p e r s o n n...

Страница 7: ...base that fasten the cabinet to the base See figure 1 1 Items needed for the connection of the extended battery cabinet to the EXL 1000 UPS are contained within the extended battery cabinet housing S...

Страница 8: ...s included with the EXL 1000 UPS to facilitate bringing that unit from it s shipping base to floor level Use this same ramp to move the extended battery cabinet off its shipping base CAUTION Do not le...

Страница 9: ...l and NEC code to the conduit landings of the EXL 1000 UPS and the extended battery cabinet Using the rightmost hole on the UPS landing and the leftmost landing on the extended battery cabinet will al...

Страница 10: ...er wire unmarked and this will identify this wire as the negative battery lead wire Run black and green wires through conduit Wires should extend approximately 6 inches out of conduit Fasten conduit f...

Страница 11: ...block With flat blade screw driver connect unmarked wire to battery negative terminal block With flat blade screw driver connect green yellow wire to ground yellow green terminal block Repeat these p...

Страница 12: ...153226 01 Figure Wiring the extended battery cabinet to the UPS landing 1 4 5 kVA Figure Wiring the extended battery cabinet to the UPS landing 1 5 7 and 10 kVA 1 6 EXL 1000 UPS Extended Battery Cabin...

Страница 13: ...applying 24Vdc or 24Vac across the XR3 emergency off terminal blocks 1 and 4 figure 1 5 Figure Connection diagram for MX shunt trip to terminal block XR3 1 6 NOTE If the EXL 1000 UPS was not facory c...

Страница 14: ...This page left blank intentionally 1 8 86 153226 01 EXL 1000 UPS Distribution Cabinet...

Страница 15: ...00 Extended Battery Cabinet Installation Manual 86 153226 01 I would like to report the following problems with this document __________________________________________________________________________...

Страница 16: ......

Страница 17: ......

Страница 18: ......

Отзывы: