86-153226-01
1 — 5
Installation manual
Figure
P r e p a r i n g t h e c o n d u i t w i r e b e f o r e c o n n e c t i n g t o U P S
1-3
The procedure to follow in the electrical installation of the
extended battery cabinet with conduit cables is as follows:
•
Connect conduit fitting on one end of conduit cable
landing on UPS. (figure 1-4).
•
With a flat blade screw driver connect red tape marked
wire to battery (+) positive terminal block.
•
With flat blade screw driver connect unmarked wire to
battery (-) negative terminal block.
•
With flat blade screw driver connect green/yellow wire
to ground yellow/green terminal block.
•
Repeat these procedures on battery cabinet end.
•
Replace conduit landing plates on UPS and battery
cabinet.
•
Turn on battery cabinet circuit breaker and UPS battery
circuit breaker.
•
On UPS switch maintenance bypass switch to
NORMAL position and press green button on front of
UPS to transfer load back from bypass to UPS inverter.
(see figure 1-2)
1.3.3
Wiring the extended
battery cabinet to
the UPS landing