![MG Energy Systems LFP Series Скачать руководство пользователя страница 44](http://html1.mh-extra.com/html/mg-energy-systems/lfp-series/lfp-series_manual_1782740044.webp)
MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands
+31 (0)58 750 89 47 | [email protected] | www.mgenergysystems.eu
Innovation
in energy storage
Current
Table 17 Current boundary limits slave BMS
Name
Action
Boundary condition
Time
Charging over current warning
Set
> 1.0C
10 sec.
Clear
<= 1.0C
10 sec.
Discharging over current warning
Set
> 2.0C
> 1C
10 sec.
Clear
<= 2.0C
<= 1C
10 sec.
Balancing
Table 18 Balancing boundary limits slave BMS
Name
Boundary condition
Time
Offset cell voltage
> 50 mV
5 min.
Balancing cell voltage
>= 3350 mV
5 min.
Battery pack current
current within ±5% battery
capacity
5 min.