BOUNDARY LIMITS
The boundary limits that are used by the master for the battery modules are listed in this chapter. A level will
be triggered when a boundary condition is true for a defined period of time.
Battery thresholds are compatible with the following master BMS firmware versions or higher:
Master HV 1.14 or higher
Master LV 1.24 or higher
11.1
Limits
Boundary limits are defined to keep the battery within manufacturer’s specifications.
The tables with the boundary limits consist of:
Name, description of the situation;
Action, action on respond of the boundary, set/clear or failsafe;
Boundary condition, contains a value that is needed for an action in combination with the time;
Time that the boundary condition has to be present before it will be triggered. Times indicated with
“+” start counting if the previous boundary condition above is set.
Cell voltage
Table 13 Cell voltage boundary limits slave BMS
Name
Action
Boundary condition
Time
Almost charged
Set
>= 3440 mV
10 sec.
Clear
< 3390 mV
10 sec.
Charged
Set
>= 3520 mV
+10 sec.
Clear
< 3440 mV
10 sec.
Over voltage warning
Set
>= 3600 mV
+20 sec.
Clear
< 3520 mV
20 sec.
Over voltage critical
Failsafe
>= 3650 mV
+5 sec.
Almost discharged
Set
<= 3075 mV
10 sec.
Clear
> 3125 mV
10 sec.
Discharged
Set
<= 2800 mV
+10 sec.
Clear
> 3075 mV
10 sec.
Under voltage warning
Set
<= 2600 mV
+20 sec.
Clear
> 2800 mV
20 sec.
Under voltage critical
Failsafe
<= 2400 mV
+5 sec.