Innovation
in energy storage
Cell temperature charging
Table 14 Cell temperature charging boundary limits slave BMS
Name
Action
Boundary condition
Time
Over temperature alert
Set
>= 43 °C
5 sec.
Clear
< 42 °C
5 sec.
Over temperature
Set
>= 45 °C
+20 sec.
Clear
< 43 °C
20 sec.
Over temperature critical
Failsafe
>= 50 °C and charge current
> 5% battery capacity
+60 sec.
Under temperature alert
Set
<= 1 °C
5 sec.
Clear
> 2 °C
5 sec.
Under temperature
Set
<= 0 °C
+20 sec.
Clear
> 1 °C
20 sec.
Under temperature critical
Failsafe
<= -5 °C and charge current
> 5% battery capacity
+60 sec.
Cell temperature discharging
Table 15 Cell temperature discharging boundary limits slave BMS
Name
Action
Boundary condition
Time
Over temperature alert
Set
>= 53 °C
5 sec.
Clear
< 52 °C
5 sec.
Over temperature
Set
>= 55 °C
+20 sec.
Clear
< 53 °C
20 sec.
Over temperature critical
Failsafe
>= 60 °C
+60 sec.
Under temperature alert
Set
<= -19 °C
5 sec.
Clear
> -18 °C
5 sec.
Under temperature
Set
<= -20 °C
+20 sec.
Clear
> -19 °C
20 sec.
Under temperature critical
Failsafe
<= -25 °C and discharge current
> 10% battery capacity
+60 sec.
Power terminal temperature
Table 16 Power terminal temperature boundary limits slave BMS
Name
Action
Boundary condition
Time
Over temperature alert
Set
>= 60 °C
5 sec.
Clear
< 59 °C
5 sec.
Over temperature
Set
>= 70 °C
+20 sec.
Clear
< 60 °C
20 sec.
Over temperature critical
Failsafe
>= 80 °C
+60 sec.