Wiring allocation, AVE (absolute value encoder) plug
6.4 / 2
The numbers on the plug are also the wire-numbers.
4:
Safety circuit input
5:
RS 485 B
6:
GND
7:
RS485 A
8:
Safety circuit output
9:
7...18V
DC
AVE (absolute value encoder) plug terminal (7-12)
6.4 / 3
C:
Thermal element in the drive
D:
Manual emergency control
(emergency crank or emergency chain)
6.5 Check the system
Check the direction of travel
☞
Drive the door in the CLOSED direction.
The operator must close the door.
☞
Drive the door in the OPEN direction.
The drive must open the door.
If the direction of movement of the door does not match the
button commands, change the direction of rotation.
The direction of movement must then be checked again.
REFERENCE
Please refer to the control unit operating manual for
instructions on changing the direction of rotation.
Check the limit switch settings
☞
Drive the door to the CLOSED end position.
The drive must stop in the desired position.
☞
Drive the door to the OPEN end position.
The operator must stop in the desired position.
☞
Check the seat of the fixing screws.
Check the mechanical functions
After assembling and installing all components the functions
of the system must be checked.
☞
Check all the functions of the system.
☞
Check that the operator runs smoothly.
☞
Check whether the operator is leaking oil.
If the operator makes unusual noises or leaks oil:
− The operator must be taken out of service immediately,
− The customer service must be informed.