Configure User Preferences 
(continued)

 

 
 
 

 

 

 

213 USER PREFERENCES 
 High Discharge Pressure 
Alarm Pressure 
[185] psi          0-999

 

 

The pressure at or above which will cause a High Pressure alarm condition 

 

 

 

214 USER PREFERENCES 

 High Discharge Alarm 
Pressure Time Delay 
[ 5]seconds      0-99 

 

The amount of time the pressure must be at or above the set pressure before the 
alarm condition is activated. 

 

 

 

215 USER PREFFENCES 
  Low Discharge Pressure 
 Alarm Option 
[No]   

 

 

This setting is used to monitor the system pressure and turn on the LOW 
PRESSURE LED and sound an alarm if it drops below a preset pressure. 

 

 

 

216 USER PREFERENCES 
 Low Discharge Pressure 
Alarm Pressure 
[45] psi          0-999

 

 

The pressure at or below which will cause a Low Pressure alarm condition 

 

 

 

217 USER PREFERENCES 

 Low Discharge Alarm 
Pressure Time Delay 
[ 5]seconds      0-99 

 

The amount of time the pressure must be at or below the set pressure before the 
alarm condition is activated. 

 

 

 

218 USER PREFERENCES 

 No Load Amps % 
 Of FLA 
[10]             0-99 

 

The % of  motor full load current at which or below that will cause an event to be 
logged indicating a No Load Motor Condition. 

 

 

 

218 USER PREFERENCES 

 No Load Time 
 Delay 
[ 5]seconds      0-99 

 

The amount of time the motor current must be at or below the set level before the 
event condition is logged. 

 

 

 

220 USER PREFERENCES 
LCD Back Light Mode 
        0=Always on 
[0]]    1=Power Save

 

 

Set to Always on or to Power Save if it is desired to have the backlight 
automatically shut off when no buttons have been pressed for a preset period of 
time.  

 

 

 

221 USER PREFERENCES 
Language Select 
 
[English]

 

 

Set to English or Spanish 

 

 

 

222 USER PREFERENCES 
Change User Password 
Level 1 
[****]

 

 

Used to set the password necessary to access the System config screens. 

 

 

 

223 USER PREFERENCES 
Reversed Phase 
Order (1-3-2) 
[No] 

 

Used to change the phase sequence sensing of the incoming power. If a Phase 
reversal alarm occurs on initial installation and the motor is turning the correct 
direction, change this setting to YES to reset the alarm indication. 

 

Содержание MP430 Series

Страница 1: ...Laboratories and approved by Factory Mutual Research Corporation Sizes range from 15 to 700 horsepower 200 to 600 volts 50 Hz These controllers are for use on Reduced Voltage type installations Only t...

Страница 2: ...es by 20 character display with large character backlit Liquid Crystal Display LCD capable of being read in both direct sunlight or dark lighting conditions 12 pushbuttons for easy screen navigation s...

Страница 3: ...the following data recorded with the event alarm providing an accurate record of events Time and Date of Event or Alarm System Pressure Descriptive Text Message of the Event Alarm Motor Running Statu...

Страница 4: ...t status LED s to provide visual indication of each discrete input s or output s on off status One RS232 Serial Port One USB 1 0 Port One RS485 Serial Port All wiring terminals on PCB s shall be remov...

Страница 5: ......

Страница 6: ......

Страница 7: ......

Страница 8: ......

Страница 9: ...0 Electric Motor Driven Fire Pump Controllers TABLE OF CONTENTS PART I General Information PAGE 3 PART II Functions PAGE 3 PART III Operation of the Controller PAGE 4 PART IV Installation Test Procedu...

Страница 10: ...Page 2 of 25 THIS PAGE IS BLANK...

Страница 11: ...provided for Transfer Switch in Normal Transfer Switch in Emergency and Emergency Iso Sw Open In addition the mode buttons have LED s on the button indicating Auto Manual Test or Off mode 12 additiona...

Страница 12: ...pressure if the Solenoid Drain Valve Option Screen 108 is selected If the Solenoid Drain Valve Option is set to NO the unit will start automatically similar to the Deluge Valve switch start feature Fa...

Страница 13: ...up for the ramp stop option Screen 106 the motor will ramp down in speed over a fixed time delay Screen 107 until it stops Note When using the emergency manual start handle the soft start unit may di...

Страница 14: ...eaker Shunt Trip Out 03 Start Contactor relay if applicable Out 04 Run Contactor relay Out 05 Start signal to Soft Start Model MP700 only Out 06 Power to Soft Start Model MP700 only In 01 Emergency St...

Страница 15: ...gnal the pump will run for the length of time left on the Auto Stop Timer and then will stop automatically g AN ADJUSTABLE SEQUENTIAL START TIMER IS SUPPLIED FOR MULTIPLE PUMP INSTALLATION Normally th...

Страница 16: ...Mode Change The operational mode that the controller is in can be changed by pressing the AUTO MANUAL or OFF buttons An LED will illuminate on the appropriate button indicating the mode of operation t...

Страница 17: ...arm Occurred 10 16 04 06 49 03 3 EVENT LOG Supvr Power Failure Alarm Cleared 10 16 04 07 09 48 PRESSURE LOG 10 16 04 17 52 45 112 psi Skip Rate EACH PRESSURE LOG 10 16 04 17 52 30 112 psi Skip Rate EA...

Страница 18: ...SYSTEM SETPOINTS Pump Automatic Stop Enabled Yes 105 SYSTEM SETPOINTS Pump Minimum Run Time 30 minutes 30 99 109 SYSTEM SETPOINTS Automatic Weekly Test Run Yes 101 SYSTEM SETPOINTS Pump Start Pressur...

Страница 19: ...ER PREFERENCES No Load Amps of FLA 5 0 99 317 TECH SCREENS Motor Run of FLA 20 0 99 319 TECH SCREENS Overload Alarm of FLA 125 100 199 320 TECH SCREENS Overload Alarm Time Delay 3 sec 0 99 322 TECH SC...

Страница 20: ...r descriptions on the functionality of each set point 1 SYSTEM STATUS B1 PRES STRT AB 460V 110 100 BC 461V psi psi AC 460V SYSTEM LOGS 1 Alarm Log 2 Event Log 3 Pressure Log 1 CONFIG 1 SYSTEM SETPOINT...

Страница 21: ...s 1 ALARM LOG Pump Failed To Start Alarm Occurred 10 16 04 07 32 15 1 EVENT LOG System in Off Mode Occurred 10 16 04 13 15 15 PRESSURE LOG 10 16 04 17 52 45 112 psi Skip Rate EACH 1 ALARM DETAILS Pump...

Страница 22: ...ou have connected to Typical Event Alarm Log Message Printout 1 EVENT LOG Superv Power Failure Alarm Occurred On 10 16 04 07 32 15 PRINT OPTIONS 1 PRINT THIS EVENT 2 PRINT EVENT RANGE 10 BEFORE 10 AFT...

Страница 23: ...vigate to the configuration set point screen that contains the value that needs to be changed 2 Press CHANGE ENTER If a password has not been entered for a while the ENTER PASSWORD screen will be disp...

Страница 24: ...g all set points only Aux 01 User Programs 501 through 515 will be printed To print any of the remaining eleven aux alarm settings press PRINT when inside the appropriate Aux alarm and select 2 for 2...

Страница 25: ...per NFPA 20 Only active if 104 above is set to Enabled 106 SYSTEM SETPOINTS Ramp Stop Option Time M700 Yes When set to Yes and the controller is set for Model MP700 the controller will stop the pump...

Страница 26: ...rt Time Delay 1 minutes 0 999 The amount of time the controller will delay starting of the pump on loss of the 120VAC Supervisory power source 118 SYSTEM SETPOINTS Pressure Transducer Failure Pump Sta...

Страница 27: ...TS Deluge Valve Pump Start No If enabled this setting activates the logic to monitor an optional deluge valve dry contact opening ie normally closed contact that opens to start pump that will start th...

Страница 28: ...ENCES Time Between Pressure Log Samples 15 seconds 15 999 The frequency at which system pressure is automatically logged Normally set to 15 seconds Lower values will increase the number of logged pres...

Страница 29: ...e before the alarm condition is activated 218 USER PREFERENCES No Load Amps Of FLA 10 0 99 The of motor full load current at which or below that will cause an event to be logged indicating a No Load M...

Страница 30: ...System was placed in Manual mode Auto Test Start Occurred An automatic pump test sequence was started while in Auto mode by either the weekly program clock function or a user pressing the TEST button...

Страница 31: ...or Ajar List of possible internal variables used as inputs for aux alarm user programs 30 Pump Running 31 Power Available 32 Phase Reversal 33 Motor Overload 34 Remote Start 35 Local Start 36 Pump On...

Страница 32: ...r tear the end off against the paper tear bar and carefully pull the remaining paper backwards from the rear of the mechanism mounting chassis until the free end emerges Press the paper roll retaining...

Страница 33: ...ridge ensuring that the paper lies between the ribbon and the steel printer platen Check that the ribbon cartridge spindle is correctly seated over the printer ribbon drive shaft and snap the cartridg...

Отзывы: