Page 20 of 25
Configure User Preferences
201 USER PREFERENCES
Set System Real
Time Clock
[17:03:52]
Set the current controller clock (24 hour clock).
202 USER PREFERENCES
Set System Date
[12/31/99]
Set the current controller date.
203 USER PREFERENCES
Set System Day
Of The Week
[Monday ]
Set the local day of the week.
204 USER PREFERENCES
Log System Pressure
Drop Events
[Yes ]
When this feature is enabled, the controller will log the current system pressure in
the event log when system pressure has dropped below the set pressure value.
Typically set to “No” as not to needlessly fill up the event log.
205 USER PREFERENCES
System Pressure Drop
Needed to Log Event
[ 60.0]psi 0-999
The desired pressure setting that will cause a log of system pressure in addition to
the normal periodic logging of system pressure.
206 USER PREFERENCES
System Pressure Drop
Event Time Span
[ 5] seconds 0-20
The amount of time the pressure must be above the pressure setting in screen 205
before the Pressure Drop Event is logged as being cleared.
207 USER PREFERENCES
Time Between
Pressure Log Samples
[ 15] seconds 15-999
The frequency at which system pressure is automatically logged. Normally set to
15 seconds. Lower values will increase the number of logged pressures and fill up
the memory in a shorter period of time.
208 USER PREFERENCES
Auto Print Each
Pressure Log Sample
[No ]
When set to Yes, each pressure log entry will be printed as it occurs. This should
be set to No to save printer paper and wear on the printer.
209 USER PREFERENCES
Auto Print Each
Event Log Entry
[No ]
When set to Yes, each event log entry will be printed as it occurs. This should be
set to No to save printer paper and wear on the printer.
210 USER PREFERENCES
Selective Range
Printing
[ 1] Before 1-99
This setting will determine the start point of print range of the pressure, alarm, or
event log based on which log entry is currently being viewed.
211 USER PREFERENCES
Selective Range
Printing
[ 1] After 1-99
This setting will determine the stop point of print range of the pressure, alarm, or
event log based on which log entry is currently being viewed.
212 USER PREFFENCES
High Discharge Pressure
Alarm Option
[No]
This setting is used to monitor the system pressure and sound an alarm if it rises
above a preset pressure.
Содержание MP430 Series
Страница 5: ......
Страница 6: ......
Страница 7: ......
Страница 8: ......
Страница 10: ...Page 2 of 25 THIS PAGE IS BLANK...