Page 23 of 34
File Name:
Doc#586p.docx
Low Pressure Start
Occurred
Cleared
A low pressure start was attempted because of a low pressure reading from the
transducer or optional pressure switch while in Auto mode.
Low Press Condition
Occurred
Cleared
System pressure dropped below the start pressure or the optional pressure switch
indicates a low pressure condition. This can be logged in all modes of operation.
Deluge Start
Occurred
Cleared
A deluge start signal was received while in Auto mode.
Controller Reboot
Occurred
DC power was restored to the FD4 microprocessor.
Pressure Drop
Occurred
Cleared
If setpoint #204 is set to yes, this event gets recorded when the system pressure
drops below the setting in setpoint #205.
Low Intake Pressure
Shutdown Occurred
Shutdown Cleared
If the low intake shutdown option is enabled in setpoint #116, a low suction
signal will stop the engine.
Auxiliary Alarm
Occurred
Cleared
Indicates one of the aux alarms occurred as programmed in the user programs and
was set to record in the event or alarm log but the text message assigned was 0.
See Aux Alarm Text List Messages below for possible auxiliary alarm messages.