213 USER PREFERENCES
Language Select
0=English 1=Spanish
[English]
Set to English or Spanish
214 USER PREFERENCES
Change User Password
Level 1
[****]
Used to set the password necessary to access the System config screens.
215 USER PREFERENCES
Save All Settings
to SD card
[No]
Used to save auxiliary alarm configuration parameters to the SD card
216 USER PREFERENCES
Load All Settings
from SD card
[No]
Used to load auxiliary alarm configuration parameters from the SD card
217 USER PREFERENCES
Pressure Units
[psi]
Used to select between psi, bar and kg/cm2 as the display of pressure
218 USER PREFERENCES
Engine running chrg
failure alarm
[ No]
Used to select whether the charger failure alarm will be active while the
engine is running or not.
219 USER PREFERENCES
Charger failure
delay time
[ 5]sec 0-999
Used to select the time delay before the controller will signal an alarm on the
charger failure after the contacts close on the battery charger.
220 USER PREFERENCES
Modbus Address
[001] 0-255
Sets the Modbus Address when turned on via screen 221
221 USER PREFERENCES
Modbus Enabled
(Disables Printer)
[ No]
Turns on the Modbus protocol via the RS485 and turns off the ASCII text
output for the printer.
222 USER PREFERENCES
Modbus/Printer Baud
[ 9600]
Baud Rate for the Modbus or Printer, depending on which is selected in
screen 221
223 USER PREFERENCES
Modbus Parity
[None]
Parity setting for the Modbus, either Even or Odd
224 USER PREFERENCES
RESTART
WIFI
[No]
Restart
Wifi
communication