Page 12 of 34
File Name:
Doc#586p.docx
Note: Sample settings shown below. Not to be used to program controller for operation. Consult factory for correct settings for
the site conditions.
303 TECH SCREENS
Energized To Stop
Fuel Solenoid Time
[10]seconds 0-99
304 TECH SCREENS
Engine Condition
Alarm Delay Time
[99]seconds 1-99
305 TECH SCREENS
Nominal Battery
Voltage
[24]VDC 10-99
306 TECH SCREENS
Battery Low Voltage
Alarm Trip Voltage
[12.0]VDC 6-99
307 TECH SCREENS
Battery Low Voltage
Alarm Trip Time
[ 2]seconds 0-99
308 TECH SCREENS
Change Tech Password
[******]
309 TECH SCREENS
Password Logout
Time
[ 5] minutes 1-15
317 TECH SCREENS
Alarm Log 1/10
Event Log 1/1569
Pr. Log 1/25123
316 TECH SCREENS
Alarm resound timers
4Hrs 0Min 0Sec
24Hrs 0Min 0Sec
314 TECH SCREENS
Load OID Hardware
Test Mode
[NO ]
313 TECH SCREENS
Annunciator Sequence
[STND]
310 TECH SCREENS
System Commissioned
Date
[31/12/99] DD/MM/YY
2 CONFIG
1) ANALOG SIGNALS
2) AUX USER PROGRAMS
1 CONFIG
1) SYSTEM SETPOINTS
2) USER PREFERENCES
3) TECH SCREENS
207 USER PREFERENCES
Time Between
Pressure Log Samples
[ 15] seconds 15-999
206 USER PREFERENCES
Low Pressure Event
Reset Time
[15] seconds 0-20
205 USER PREFERENCES
Low Pressure Event
Trip Pressure
[ 60.0]psi 0-999.9
204 USER PREFERENCES
Log System Pressure
Drop Events
[Yes]
203 USER PREFERENCES
Set System Day
Of The Week
[Sun]
202 USER PREFERENCES
Set System Date
[08/10/10] DD/MM/YY
212 USER PREFERENCES
LCD Back Light Mode
0=Always on
[0]] 1=Power Save
213 USER PREFERENCES
Language Select
0=English, 1=Spanish
[0]
214 USER PREFERENCES
Change User Password
Level 1
[****]
201 USER PREFERENCES
Set System Real
Time Clock
[17:03:52]
102 SYSTEM SETPOINTS
Engine Stop
Pressure
[110.0]psi 0-999.9
112 SYSTEM SETPOINTS
Power Failure Engine
Start Delay Time
[ 1] minutes 0-500
115 SYSTEM SETPOINTS
Shutdown On Low
Intake Contact Type
[NO ]
114 SYSTEM SETPOINTS
Fail to start input
MB22 for unavailable
[No ]
113 SYSTEM SETPOINTS
Pressure Transducer
Failure Engine Start
[Yes]
111 SYSTEM SETPOINTS
Power Failure Engine
Startup
[No]
108 SYSTEM SETPOINTS
Auto Weekly Engine
Test Start Time
[10:00:00]
109 SYSTEM SETPOINTS
Auto Weekly Test
Length Of Run Time
[30] minutes 30-99
110 SYSTEM SETPOINTS
Auto Weekly Test
Oil/Water Shutdown
[No]
103 SYSTEM SETPOINTS
Engine Start Delay
Time
[ 1] seconds 1-999
104 SYSTEM SETPOINTS
Engine Automatic
Stop Enabled
[Yes]
105 SYSTEM SETPOINTS
Engine Minimum
Run Time
[30]minutes 30-99
106 SYSTEM SETPOINTS
Automatic Weekly
Engine Test Run
[No]
101 SYSTEM SETPOINTS
Engine Start
Pressure
[100.0]psi 0-999.9
ANALOG INPUT COUNTS
649 1176 1221 12
12
422 ANALOG SIGNALS
Analog Input 3 1225
Minimum Counts
[ 0]
421 ANALOG SIGNALS
Analog Input 03
Offset:
[ 0.0000]
420 ANALOG SIGNALS
Analog Input 03
Slope:
[0.0352500]
412 ANALOG SIGNALS
Analog Input 2 1174
Minimum Counts
[ 0]
411 ANALOG SIGNALS
Analog Input 02
Offset:
[ 0.0000]
410 ANALOG SIGNALS
Analog Input 02
Slope:
[0.0352500]
402 ANALOG SIGNALS
Analog Input 1 651
Minimum Counts
[ 200]
401 ANALOG SIGNALS
Analog Input 01
Offset:
[- 76.1904]
400 ANALOG SIGNALS
Analog Input 01
Slope:
[0.3401360]
502 AUX SETPOINTS
Aux User Program # 1
Input Number
[30] 0-70
512 AUX SETPOINTS
Aux User Program # 1
Output3 Number
[ 0] 0-24
514 AUX SETPOINTS
Aux User Program # 1
Text Message Number
[ 0] 0-32
513 AUX SETPOINTS
Aux User Program # 1
Record In Event Log
[No ]
507 AUX SETPOINTS
Aux User Program # 1
Horn Enabled
[No ]
511 AUX SETPOINTS
Aux User Program # 1
Output2 Number
[ 0] 0-24
510 AUX SETPOINTS
Aux User Program # 1
Output1 Number
[ 0] 0-24
508 AUX SETPOINTS
Aux User Program # 1
Horn Silence
[No ]
509 AUX SETPOINTS
Aux User Program # 1
LED Number
[ 0] 0-24
504 AUX SETPOINTS
Aux User Program # 1
Trip Time
[ 0]sec 0-999
505 AUX SETPOINTS
Aux User Program # 1
Reset Time
[ 0]sec 0-999
506 AUX SETPOINTS
Aux User Program # 1
Auto Reset Enabled
[Yes]
503 AUX SETPOINTS
Aux User Program # 1
Input Contact Type
[NO ]
501 AUX SETPOINTS
Aux User Program # 1
Enabled
[No]
107 SYSTEM SETPOINTS
Auto Weekly Engine
Test Day Of The Week
[Mon]
215 USER PREFERENCES
Save ALL settings
to SD memory card
[No ]
216 USER PREFERENCES
Load ALL settings
from SD memory card
[No]
424 BATTERY 1
Constant A
xA^3 + xB^2 + xC + D
[ 0.0000]
425 BATTERY 1
Constant B
xA^3 + xB^2 + xC + D
[ 0.0000]
426 BATTERY 1
Constant C
xA^3 + xB^2 + xC + D
[ 0.00978]
427 BATTERY 1
Constant D
xA^3 + xB^2 + xC + D
[- 0.05642]
428 BATTERY 1
Volts per count
[1.0000000]
318 TECH SCREENS
Dump Valve
Delay time
[0]s 0-999
217 USER PREFERENCES
Pressure Units
[bar]
218 USER PREFERENCES
Engine Running chrg
failure alarm
[No]
515 AUX SETPOINTS
Aux User Program # 1
Engine Run Dependent
[ ]
24v Defaults
FD4e v5.00
211 USER PREFERENCES
Enable Remote
Keypad
[ No]
311 TECH SCREENS
DOUBLE SKINNED
FUEL TANK
[No]
312 TECH SCREENS
ELECTRONIC ENGINE
[No]
OID Screen Map (continued)