Chimney cavity vent installation

Cut a hole as detailed no higher than 230mm above the base of the fire as 
illustrated in the diagram. The minimum open vent area of 14,400mm

2

 with 

a maximum height of 230mm must be cut through the chimney.

Suitable precautions will be necessary to prevent rodents and debris from 
entering or restricting the air vent. If a grilled vent cover is used, please 
ensure the minimum vent area is maintained through the grille itself.

It is the responsibility of the installer to ensure that the requirements of 
New Zealand Building Code Clause E2 (External Moisture) are complied with.

Pioneer masonry vent cover kit. 
Installation instructions:

• 

Cut a hole through the masonry chimney 300mm wide x 133mm high. 
Please note that this is an external dimension and the base of the hole 
must slope up at least a 1/6 gradient as illustrated.

• 

Cut a weather seal groove 25mm above the vent hole at a minimum 
depth of 18mm x 400mm long (centred with the air vent)

• 

Place silicon around the top and side flanges of the vent cover and 
position into the hole and bead off around the perimeter

• 

Fill the weather seal groove with silicon and embed the weather strip 
fully into the silicon to ensure weather-tightness.

Chimney vent requirements

230mm M

aximum heigh

A

bo

ve base of fir

e cabinet

55mm

133mm

25mm

10

Stainless Steel

Masonry Vent

Cover

Weather Strip

Silicon seal

Anti vermin 

mesh

Ultra Insert Wood fire

Chimney cavity venting requirements

Maximum vent 

height / minimum 

open vent area of 

144cm

/ 14,400mm

2

230mm

•  An air vent is required on the rear face of the masonry cavity 

enclosure. The top of this vent must be no higher than 230mm 
above the floor and must have an overall minimum surface area of 
14,400mm

2

.

•  Suitable precautions will be necessary to prevent rodents and 

debris from entering or restricting the air vent. If a grilled vent 
cover is used, please ensure the minimum vent area is maintained 
through the grille itself.

Note: Silicon, chimney vent cover and weather strip are not included as 
they are supplied by the installer. Pioneer manufacture a stainless steel 
masonry vent cover kit to complete installation. Details for the specific 
vent dimensions and Pioneer kit installation are detailed below.

 

CAUTION! 

Important Information

Pioneer masonry vent cover

Pioneer weather strip

Weather seal groove 400mm long

Содержание Ultra Insert

Страница 1: ...quirements 9 Getting to know your Metro 10 Replacement parts accessories 11 Operating your Metro 11 Cleaning and maintenance 13 Troubleshooting 14 Metro warranty 15 Ultra Insert Wood Fire Wood Fire In...

Страница 2: ...lue pipe exposed A rear cavity vent is required Please see detail in Diagram 1 opposite with full cavity vent requirements and installation detailed on page 8 of this manual In New Zealand the Metro U...

Страница 3: ...lation instructions detailed on page 6 proceed and fit the flue with All JOINTS SEALED and riveted with a minimum of three stainless steel or monel rivets on each joint 7 With Pioneer fire cement appl...

Страница 4: ...or cabinet Ensure the fan rotates freely 4 Rotate the door handle fully anti clockwise before placement of the fascia The inner fascia slips snugly into the cabinet with the Top Rail of the fascia res...

Страница 5: ...s in its correct position in the top chamber of the firebox It should be resting on four support lugs two on each side of the firebox The baffle must be hard back against the rear wall of the firebox...

Страница 6: ...omponents A 1 x Stainless steel weather butterfly B 1 x Stainless steel ECO Cowl top C 1 x 420mm x 240mm diameter stainless steel ECO Cowl housing D 1 x 480mm long stainless steel flue pipe extension...

Страница 7: ...eather butterfly A so the angled sections are facing up With both arms and angled sections of the stainless steel weather butterfly A facing up fit it into the stainless steel ECO Cowl top B and secur...

Страница 8: ...nd bead off around the perimeter Fill the weather seal groove with silicon and embed the weather strip fully into the silicon to ensure weather tightness Chimney vent requirements 230mm Maximum height...

Страница 9: ...de of the door opening making the minimum floor protector width 825mm The insulated floor protector must project from behind the fascia the distance specified I in the table below Minimum projection i...

Страница 10: ...baffle plate promet extension white board on the baffle plate It is critical that the fire not be operated with cracked or broken door glass It is critical that the fire is operated with the fan switc...

Страница 11: ...easoned 12 months later Burning properly seasoned dry fuel will result in Less ash buildup Less emission into the environment Less creosote that can cause a host of issues Maintain a clean flue system...

Страница 12: ...latch After 2 minutes with the kindling well alight fully close the door Intermediate load with air control fully open Approximately 40 minutes after lighting once remaining fuel has formed hot coals...

Страница 13: ...epends on the density and cleanliness of your fuel To remove the excess ash your Metro should not be operating Open the door and using a hearth shovel or similar empty the excess ash directly into a s...

Страница 14: ...We highly recommend the Metro ECO Cowl is fitted as this will increase the draw If you already have an ECO Cowl and smoke is still entering the room please add another 600mm length of flue pipe Downd...

Страница 15: ...the life span will be reduced If your Metro wood fire has been neglected by not being regularly maintained and serviced warranty may be declined It is critical the fire not be operated with over worn...

Страница 16: ......

Отзывы: