MI 2087 Instaltest 61557
Measurement instructions
41
•
Store displayed results for documentation purpose; see instructions how to store
it in chapter 4.1. Storing of test results.
If RCD trips during Contact voltage measurement,
rcd
message will be displayed
blinking way.
Notes!
•
Nominal input voltage range is 100
÷
264 V, if input voltage is out of the range,
the voltage value equipped with
“!”
mark will be displayed after pressing
START
key. Warning sound signal will be effected too.
•
The instrument will exchange L and N terminals automatically, if N/L2 and L/L1
test leads (Universal test cable) are connected reversed way or terminals on
tested wall plug are reversed or Plug commander is turned around.
•
If test result is out of display range,
>1999
Ω
Ω
Ω
Ω
message will be displayed!
•
Specified accuracy of tested parameters is valid only, if mains voltage is stabile
during the measurement!
•
bat
message, displayed during or after finishing the measurement means
batteries are too weak to guarantee correct result. Replace the batteries.