MI 3102(H) BT
Eurotest
XE
Technical specifications
94
10.6
Line impedance and prospective short-circuit current /
Voltage drop
Line impedance
Measuring range according to EN 61557 is 0.25
9.99k
.
Measuring range (
)
Resolution (
)
Accuracy
0.00
9.99
0.01
(5 % of r 5 digits)
10.0
99.9
0.1
100
999
1
10 % of reading
1.00 k
9.99 k
10
Prospective short-circuit current (calculated value)
Measuring range (A)
Resolution (A)
Accuracy
0.00
0.99
0.01
Consider accuracy of line
resistance measurement
1.0
99.9
0.1
100
999
1
1.00 k
99.99 k
10
100 k
199 k
1000
Test current (at 230 V) ........................... 6.5 A (10 ms)
Nominal voltage range ........................... 93 V
134 V (45 Hz
65 Hz)
185 V
266 V (45 Hz
65 Hz)
321 V
485 V (45 Hz
65 Hz)
Voltage drop (calculated value)
Measuring range (%)
Resolution (%)
Accuracy
0.0
99.9
0.1
Consider accuracy of line
impedance measurement(s)*
Z
REF
measuring range .....................................
0.00 Ω
20.0 Ω
for more information about calculation of voltage drop result