Fault loop impedance measurement procedure
Select the
ZLOOP
function using the function selector keys.
Set sub-function to
Zloop
or
Zs rcd
using the
UP / DOWN
keys.
Select test
parameters
(optional).
Connect
test cable to the instrument.
Connect
test leads to the item to be tested (see
Press the
TEST
key to perform the measurement.
Store
the result by pressing the
MEM
key (optional).
Figure 5.28: Example of loop impedance measurement result
Displayed results:
Z
............... fault loop impedance
Isc
............ prospective fault current,
Lim
........... low limit prospective short-circuit current value
Prospective fault current I
SC
is calculated from measured impedance as follows:
Z
k
Un
I
SC
SC
where:
Un ......... Nominal U
L-PE
voltage (see table below),
ksc ........ Correction factor for Isc (see chapter
U
n
Input voltage range (L-PE)
110 V (93 V
U
L-PE
134 V)
230 V (185 V
U
L-PE
266 V)
Notes:
High fluctuations of mains voltage can influence the measurement results (the noise sign
is displayed in the message field). In this case it is recommended to repeat few
measurements to check if the readings are stable.
This measurement will trip-out the RCD in RCD-protected electrical installation if test
Zloop is selected.
Select Zs rcd measurement to prevent trip-out of RCD in RCD protected installation.