Installation Manual
MX15 Series
11
The input power cables and protective circuit breaker used must be large enough to handle the
input current and input voltage of the power source and must conform to local electrical codes.
Consult a qualified electrician prior to installation. Table 2-1 shows the size of the cables that may
be used per MX15 cabinet. Note that wires must be sized to accommodate the worst-case
maximum current that may occur under low line conditions. Local electrical codes may also
require different wire types and sizes. These ratings should also be used when selecting a circuit
breaker or equivalent disconnect device.
Cable lengths must not exceed twenty-five (25) feet. For lengths greater than 25 feet, calculate
the voltage drop from the following formula:
2 X DISTANCE X CABLE RESISTANCE PER FT. X CURRENT = VOLT DROP
Table 2-1: Suggested Input Wiring Sizes for each MX15 Cabinet
Nominal Line
Voltage
Load Current
@ low line
Wire Gauge (US)
Circular Mils
(Kcmils)
Metric (mm2)
480 V
25 Arms
10 AWG
11.50
5.8
400 V
30 Arms
10 AWG
11.50
5.8
230 V
52 Arms
8 AWG
18.00
9.1
208 V
58 Arms
6 AWG
26.24
13.3
CAUTION: Capacitors in the power source may hold a hazardous electrical charge
even if the power source has been disconnected from the mains supply. Allow
capacitors to discharge to a safe voltage before touching exposed pins of mains
supply connectors.
Power modules need at least 15 Minutes to discharge to safe levels before they can be
removed.
2.5 AC On/Off Circuit Breaker on MX15 front panel.
It is important to understand the purpose and operation of the On/Off circuit breaker of the MX15
located on the upper left side of the front panel. This is a 2A rated breaker that is used to engage
and protect the LV Power supply of the MX15 chassis only. The LV Power supply provides DC
bias power to the entire MX15 system. The AC input power is routed through a set of three AC
line fuses (F1-A, F1-B and F1-C) located in the lower right bottom corner of the MX15 (Looking
from the rear). (See Figure 2-2 for fuse locations). These fuses protect the MX15 amplifier and
the AC input transformer from excessive input currents. The AC input power is connected to the
input transformer through a large three-pole contactor. Removing AC power to the LV Power
Supply by opening the front panel circuit breaker (moving the lever to the down (OFF) position)
will cause this contactor to lose its coil voltage and will result in it opening and disconnecting the
input transformer and amplifier from AC mains input.
Note: If any MX15 system failure has occurred on any part of the MX15 system, AC input
power must be removed immediately and not restored until the system has been
inspected by a qualifier service technician.
Always turn off the On/Off Circuit breaker before re-applying AC input power.
Содержание MX15
Страница 2: ......
Страница 3: ......
Страница 6: ...ii This page intentionally left blank ...
Страница 14: ...Installation Manual MX15 Series 10 Figure 2 3 MX15 AC Input Connection Diagram ...
Страница 32: ...Installation Manual Rev C California Instruments MX15 Series 28 Figure 2 13 Functional Test Setup ...