50
Electrical output specifications when running on battery power
MEGALINE
1250
MEGALINE
2500
MEGALINE
5000
MEGALINE
3750
Nominal output
voltage
Output
frequency
Overload
capacity
Tolerated power
factor range of
applied load
Active output power
with linear or non-
linear load P.F. 0,7
Total harmonic
distortion of output
voltage
DC-AC conversion
efficiency with
linear load P.F. 1
and charged
batteries:
•with 50% load
•with 75% load
•with 100% load
Nominal output
power VA
230 V ± 1%
160% for 15 seconds
from 0,7 to 1
< 1%
80%
80%
80%
1250 VA
875 W
2625 W
3500 W
1750 W
2500 VA
3750 VA
5000 VA
50 Hz / 60Hz ± 1% (autosensing and/or as selected by operator)
5 - Specification
ATTENTION:
There is a danger of explosion should the batteries be replaced with the wrong type.
Dispose of used batteries as per the instructions and precautions for their disposal on the battery label!
!