44
Set capacity
Reserve Time
➧
Sets the warning signal for the end of battery
autonomy using the remaining run time
(minutes)
Advanced mode
Reserve
Time
Set capacity
Batteries
Set capacity
Battery Thresholds
➧
Sets the warning signal for the end of battery
autonomy using the battery voltage.
There are two possible settings in the
Mode
menu
If you select
Mode
–
Automatic thresholds
The UPS automatically calculates the voltage
thresholds based on the load: the UPS will
signal AUTONOMY RESERVE and END OF
AUTONOMY, respectively, below these.
If you select
Mode – Fixed thresholds
There are two options for this setting:
1) Reserve threshold
Sets the battery voltage threshold; the UPS will
signal AUTONOMY RESERVE below this
2) Exhaust threshold.
Sets the battery voltage threshold; the UPS will
signal END OF AUTONOMY below this.
Simple mode
Battery
thresholds
Set capacity
Batteries
ADVANCED MODE
SIMPLE MODE
4 - Customising the UPS operating mode