mcr FIND WING 

fire protection cut-off damper 

MERCOR SA – 

The company reserves the right to modify and change the document. Version: mcr FID WING 21.08.02.1

 

14/15 

•  the dampers are not affected by direct sunlight and UV radiation; 
•  maximum relative humidity does not exceed 80% at the temperature of + 20 ºC; 
•  the ambient temperature is between - 20 ºC and + 40 ºC; 
•  there are no vibrations. 

 

 

8. MAINTENANCE AND SERVICE (REPAIRS) 

Products manufactured by „MERCOR” SA should undergo periodic technical inspections and maintenance at least 
every  12  months  throughout  their  service  life,  i.e.  in  the  warranty  period  and  later.  Inspections  and  maintenance 
should be carried out by the manufacturer or by companies authorised to service „MERCOR” SA’s products. 
 
The obligation  to  conduct  regular  inspections  of  fire  equipment is  stipulated  in  §  3  section  3  of  the  Regulation  of 
Minister of Internal Affairs and Administration dated 7 June 2010 on the fire protection of buildings, other structures 
and areas (Dz. U. [Journal of Laws] 2010 No. 109, item 719). 
 
The recommended operations to be carried out between the inspections are as follows: 

 

check the condition of electrical connections, paying particular attention to mechanical damage; 

 

Inspections of the condition of the supply voltage for the devices, which allowed the following tolerances: 

 

24V±10% for electric actuators 

 

24V±2% for electromagnetic release mechanism 

 

230V ±10% for electric actuators 

 

230V±2% for electromagnetic release mechanism 

 

check the condition of the fire damper’s body, paying particular attention to mechanical damage; 

 

check for causes that could possibly affect the correct operation of the fire damper. 

To  enable  full  service  inspections  as  well  as  servicing,  including  servicing  under  the  warranty,  such  as  visual 
inspections  and  repairs,  the  user  has  to  ensure  physical  access  to  the  product,  e.g.  by  removing  thermal 
insulation/suspended ceilings and disassembling other systems if they prevent free access to the product, etc. 
In the case of fire dampers installed in ducts, it is recommended to make a service duct such as the mcr KRW type, 
for instance. 
If devices are installed on the roof, ensure the possibility to enter the roof (ladder or lift). 
 
For matters relating to technical inspections, maintenance and service of our products, please contact the Service 
Department of „Mercor” SA at [email protected], phone 058/ 341 42 45 (extension number 170), fax 058/341 
39 85, 8 am–4 pm (Mon–Fri). 
 

9. WARRANTY TERMS AND CONDITIONS 

1.  “MERCOR” SA grants 12 months of warranty for the equipment quality from the date of purchase, 

unless the sales contract states otherwise. 

2.  Submit each warranty claim to “MERCOR” SA in 7 days from the date of discovery of a warranty 

eligible defect 

3.  Submit warranty claims by calling at: tel. +48 58 341 42 45, by fax: +48 58 341 39 85, by e-mail: 

[email protected] or by traditional mail: “MERCOR” SA, ul. Grzegorza z Sanoka 2, 80-408 
Gdańsk, Poland. 

4.  If physical defects of equipment are found during the warranty period, “MERCOR” SA warrants and 

represents to remove them in shortest possible time from serving the written warranty claim with the 
proof of purchase or sales contract, subject to Item 10. 

5.  “MERCOR”  SA  has  the  right  to  extend  the  time  of  repair  if  the  defect  removal  is  complicated  or 

requires purchase of custom components or spare parts. 

6.  The warranty liability only covers all defects arising from causes present in the equipment at the date 

of sale. 

7.  Defects caused by improper operation or otherwise as listed in Item 10 herein, the buyer / warranty 

beneficiary will be charged with the costs of their removal. 

8.  Condition for rectifying defects is that the applicant makes the site/localisation where devices are 

installed available, in particular, ensuring: the lift in the case of devices mounted at a height above 
3m, free access to the rooms where the devices were installed and necessary revisions, dismantling 
thermal  insulation,  disassembling  suspended  ceilings,  disassembling  other  installations,  if  they 
prevent free access to the device. 

Содержание mcr FID WING

Страница 1: ...zegorza z Sanoka 2 80 408 Gdańsk tel 0 58 341 42 45 tel fax 0 58 341 39 85 OPERATION AND MAINTENANCE MANUAL Fire protection cut off damper mcr FID WING Version 21 08 02 1 FIRE VENTILATION SYSTEMS DEPARTMENT ...

Страница 2: ...ION 6 6 1 INSPECTION BEFORE THE INSTALLATION 6 6 2 FIXING HOLE 7 6 3 EMBEDDING 7 6 4 ELECTRICAL CONNECTIONS 10 7 TRANSPORT AND STORAGE CONDITIONS 11 8 MAINTENANCE AND SERVICE 11 9 WARRANTY CONDITIONS 11 Labelling used in the operation and maintenance manual Option available Option unavailable NOTE With the date of publication of the operation and maintenance manual the previous versions are no lon...

Страница 3: ...tive humidity does not exceed 80 at the temperature of 20 ºC the ambient temperature is between 20 ºC and 40 ºC there are no vibrations The device is equipped with a thermal release containing one time temperature fuses During normal operation the above mentioned element should be protected against the impact of the permissible temperature Tmax see the table below When it is exceeded the temperatu...

Страница 4: ...D WING type fire protection cut off damper has the following fire resistance EI60S S V V M T G EI120S S V V M T G EI60 S V V M T G EI120 S V V M T G E60S S V V M T G E120S S V V M T G E60 S V V M T G E120 S V V M T G Performance versions The mcr FIND WING type fire dampers may be manufactured as rectangular fire dampers round fire dampers Dimension range The mcr FID WING type dampers are manufactu...

Страница 5: ... actuation of the axial electric actuator with a return spring as the supply voltage disappears automatically by actuation of the thermal release and the power spring The structure of the system equipped with an air diffuser enables the regulation of efficiency during normal operation of the device setting the gap between the body of the mechanism and the valve plug The adjustment is made by rotat...

Страница 6: ...wing space dividing elements walls or structural floors masonry concrete walls with the minimum thickness of 100 mm brickwork walls or blockwork walls with the minimum thickness of 100 mm walls made of boards with the minimum thickness of 100 mm structural floors with the minimum thickness of 150 mm for EIS120 and 100mm for EIS60 Additionally fire dampers may be installed outside walls in dampers ...

Страница 7: ...stallation min D 100 max D 600 in the case of concrete and masonry partitions and in the ceiling and dry installation Wall Ceiling Wet installation Dry installation 6 3 EMBEDDING SETTING THE DAMPER INSTALLATION IN A PLASTERBOARD CONCRETE OR MASONRY WALL Insert the connection duct in the assembly opening so that the axis of the channel coincides with the axis of the opening The gap between the duct...

Страница 8: ...nt based mortar The manufacturer allows the use of other materials with parameters that confirm and ensure the appropriate class of fire resistance for the applied method of assembly 1 mcr FID WING damper 2 Insulating band 3 Ventilation duct 4 Mortar or mineral wool 5 Drywall 6 The 12 5mm drywall board band X Wall thickness installation of the mcr FID WING damper in plasterboard walls for EIS120 R...

Страница 9: ...ased mortar The manufacturer allows the use of other materials with parameters that confirm and ensure the appropriate class of fire resistance for the applied method of assembly 1 mcr FID WING damper 2 Insulating band 3 Ventilation duct 4 Mortar 5 Rigid walls 6 The 12 5mm drywall board band 7 Mortar or mineral wool X Wall thickness installation of the mcr FID WING damper in rigid walls for EIS120...

Страница 10: ...on plaster or cement mortar The manufacturer allows the use of other materials with parameters that confirm and ensure the appropriate class of fire resistance for the applied method of assembly 1 mcr FID WING damper 2 Insulating band 3 Ventilation duct 4 Mineral wool 5 Mortar fire resistant paint 6 Drywall 7 Rigid wall X Thickness of the wall installation of the mcr FID WING damper in dry systems...

Страница 11: ...based mortar The manufacturer allows the use of other materials with parameters that confirm and ensure the appropriate class of fire resistance for the applied method of assembly 1 mcr FID WING damper 2 Insulating band 3 Ventilation duct 4 Mortar or mineral wool 5 Drywall 6 The 12 5mm GK board band 7 Mortar 8 Air diffuser X Wall thickness installation of the mcr FID WING damper in plasterboard wa...

Страница 12: ...sure the appropriate class of fire resistance for the applied method of assembly 1 mcr FID WING damper 2 Insulating band 3 Ventilation duct 4 Mineral wool 5 Mortar fire resistant paint 6 Drywall 7 Rigid wall 8 Air diffuser X Thickness of the wall installation of the mcr FID WING damper in dry systems Recommended installation of the damper in a dry system is based on wool of min 140 kg m3 with non ...

Страница 13: ...he electrical installation connect the wires of this installation properly The connection method and basic data of electrical components are presented below Electrical connection diagram of the mcr FID WING WK1 fire damper 1 black 2 gray 4 blue 1mA 4V AC min 6A 250V AC max 7 TRANSPORT AND STORAGE CONDITIONS Fire dampers are packaged in cardboard boxes or placed on pallets Dampers are protected aga...

Страница 14: ...er systems if they prevent free access to the product etc In the case of fire dampers installed in ducts it is recommended to make a service duct such as the mcr KRW type for instance If devices are installed on the roof ensure the possibility to enter the roof ladder or lift For matters relating to technical inspections maintenance and service of our products please contact the Service Department...

Страница 15: ...nd Deterioration in the quality of coatings due to natural weathering ageing Defects caused by abrasive or aggressive cleaning agents Damage caused by aggressive external influence specifically chemical or biological in nature or when the origin of which is related to the production processing or activity carried out within the facility protected by the equipment or in its direct vicinity Wearing ...

Отзывы: