mcr FIND WING
fire protection cut-off damper
MERCOR SA –
The company reserves the right to modify and change the document. Version: mcr FID WING 21.08.02.1
13/15
1. mcr FID WING damper
2. Insulating band
3. Ventilation duct
4. Mortar *
5. Ceiling
6. Mortar / fire-resistant
paint *
7. Mineral wool *
8. Air diffuser
X Thickness of the ceiling
Y 75mm for EIS120
45mm for EIS60
installation of the mcr FID WING damper in ceilings
* Recommended installation of the damper in a dry system is based on wool of min. 140 kg / m3 with non-flammability
class A1, thickness min. 50mm and securing the joint between the wool and the wall with PROMASTOP E PASTE
or HILTI CFS-CT paint and wool with the fire-retardant PROMASTOP E PASTE or HILTI CFS-S ACR paint, as shown
in the above drawing. The recommended installation of the damper in a wet system is based on plaster or cement
mortar.
The manufacturer allows the use of other materials with parameters that confirm and ensure the appropriate class
of fire resistance for the applied method of assembly.
6.4. ELECTRICAL CONNECTIONS
Before the damper is finally mounted in the connection duct, if it has elements that require connection to the electrical
installation, connect the wires of this installation properly. The connection method and basic data of electrical
components are presented below.
Electrical connection diagram of the mcr FID WING + WK1 fire
damper
1 - black
2 - gray
4 - blue
1mA 4V AC min
6A 250V AC max
7. TRANSPORT AND STORAGE CONDITIONS
Fire dampers are packaged in cardboard boxes or placed on pallets. Dampers are protected against damage by film
or another covering material. Damper shipping may take place using any means of transport, under the condition
they are protected against weather factors. Dampers placed on means of transport should be secured against shifting
of position during transport. Before installing dampers, control each of them visually. Do not move the damper by
holding by the connection cable or put a device on a release and control mechanism. Do not hit or drop the damper.
When moving and installing, support the damper on the sides or edges of the body.
Dampers should be stored in closed rooms that provide protection against external weather conditions. In the case
dampers are stored on the ground, place them on protection pads in order to protect them against damage. Storage
should take place in rooms where:
• there is no access to dust, gases, caustic vapors and other aggressive chemical vapors that can destroy
insulating elements and structural elements;