mcr FIND WING
fire protection cut-off damper
MERCOR SA –
The company reserves the right to modify and change the document. Version: mcr FID WING 21.08.02.1
4/15
1. INTRODUCTION
The purpose of this operation and maintenance manual is to get the user acquainted with the intended use, design,
the principle of operation, correct installation and operation of the product.
The manual also includes additional information about the operating conditions, maintenance and warranty conditions
of the product.
2. THE SUBJECT OF THE MANUAL
This operation and maintenance manual concerns the entire group of fire protection cut-off dampers of type
mcr FID WING. Observing recommendations included in the manual ensures correct function of the device in terms
of fire protection of rooms as well as safety of the system users.
3. DEVICE INTENDED USE
Application
A mcr FID WING type damper may be used as a fire protection cut-off damper with a duct connection as well as a
transfer damper (installation without ventilation ducts).
The damper may not work in systems exposed to dust, except for when they are included in a special, individually
developed programme of service and technical inspections.
Fire resistance
The mcr FID WING type fire protection cut-off damper has the following fire resistance:
EI60S
/S /V /V-M
/T /G
EI120S
/S /V /V-M
/T /G
EI60
/S /V /V-M
/T /G
EI120
/S /V /V-M
/T /G
E60S
/S /V /V-M
/T /G
E120S
/S /V /V-M
/T /G
E60
/S /V /V-M
/T /G
E120
/S /V /V-M
/T /G
Performance versions
The mcr FIND WING type fire dampers may be manufactured as:
rectangular fire dampers
round fire dampers
Dimension range
The mcr FID WING type dampers are manufactured in the following dimensions - diameters:
Ø100
Ø125
Ø160
Ø200
4. DEVICE DESIGN AND PRINCIPLE OF OPERATION
Design
The mcr FID WING fire damper consists of a casing with a round cross-section, a movable cut-off partition and a
release and control mechanism that is automatically activated after the thermal fuse is actuated. The damper housing
is made of steel sheet. In the housing of the device, on its perimeter, there is a ventilation and intumescent gasket.
The cut-off partition of the damper is made of a non-flammable plate. Additionally, the damper can be equipped with
microswitches indicating the position of the device partition. The damper can also be equipped with an air valve (air
diffuser), enabling the adjustment of the parameters of the ventilation system. The device is delivered complete with
two insulating bands. The manufacturer requires the installation of the bands according to the drawings included in
the Operation and Maintenance Manual in order to obtain the declared fire resistance.