background image

Page 6

Insulation Resistance test

1. Short-circuit the + and - SUPPLY terminals in the terminal 

box.

2. Turn OFF the insulation tester. Then connect the 

insulation tester plus (+) lead-wire to the shorted SUPPLY 
terminals and the minus (-) lead wire to the grounding 
terminal. 

3. Turn ON the insulation tester power and measure the 

insulation resistance. The voltage should be applied briefly 
to verify that insulation resistance is at least 20MΩ.

4. After completing the test and being very careful not to 

touch exposed conductors. Disconnect the insulation 
tester and connect a 100kW resistor between the 
grounding terminal and the short-circuiting SUPPLY 
terminals. Leave this resistor connected at least three 
seconds to discharge any static potential. Do not touch the 
terminal while it is discharging. 

Dielectric Strength Test

a. Short-circuit the + and - SUPPLY terminals in the terminal

box.

b. Turn off the dielectric strength tester. Then connect the 

tester between the shorted SUPPLY terminal and the 
grounding terminal. Be sure to connect the grounding lead
of the dielectric strength tester to the ground terminal.

c. Set the current limit on the dielectric strength tester to 

10 mA, then turn on the power and gradually increase the 
tester voltage from '0' to the specified voltage.

d. When the specified voltage is reached, hold it for one 

minute. 

e. After completing this test, slowly decrease the voltage to 

avoid any voltage surges.

2.10 Explosion-Proof Rating

2-10-1. FM Certification

HAZARDOUS LOCATION ELECTRICAL EQUIPMENT
Equipment Rating: Explosion-Proof for use in Class I, Division 1, 
Groups A, B, C and D;
Dust- Ignition-Proof for Class II/III, Division 1, Groups E, F and G;
Nonincensive for use in Class I, Division 2, Groups A, B, C and D;
Suitable for use in Class II, Division 2, Groups E, F and G; 
and Suitable for Class III, Division 1;
Hazardous (classified) location, indoor and outdoor
(NEMA Type 4X/IP67).

2.11 EMC Conformity Standards

EMI (Emission): EN55011
EMS (Immunity): EN50082-2

Dwyer Instruments, Inc. recommends customer use metal conduit
wiring or twisted pair shield cable for signal wiring to conform with
EMC regulation, when installing the Mercoid

®

3100 transmitters.

Chapter 3 Transmitter Functions

3.1 Overview

This Chapter contains information on operating the Model 3100.
Tasks that should be performed on the bench prior to installation are
explained in this chapter.

3.2 Safety Message

Procedures and instructions in this chapter may require special
precautions to ensure the safety of the personnel performing the
operations. Potential safety issues are indicated by a warning
symbol (▲). Refer to the following safety messages before
performing an operation preceded by this symbol.

3.3 Warning

Warning
Explosion can result in death or serious injury:

• Do not remove the transmitter covers in explosion
environments when the circuit is powered.

• Transmitter covers must be fully engaged to meet
explosion-proof requirements.

Warning
Electrical shock can result in serious injury: 

• Only qualified personnel can install the transmitter.

3.4 Fail Mode Alarm

Mercoid

®

Smart Pressure Transmitter automatically and

continuously performs self-diagnostic test. If the self-diagnostic test
detects a failure, the transmitter drives the output outside of the
normal operation values. The transmitter will drive its output low
(down) or high (up) based on the position of the failure mode alarm
jumper. See Table 3.1 for output values.

[Table 3.1 Standard Alarm and Saturation Values]

Warning
Electrical shock can result in serious injury: 

• Avoid contact with the leads and terminals. High
voltage, that may be present, on leads can cause
electrical shock.

Fail Safe mode can be set via Jumper switches provided on the LCD
module or the main CPU module. The jumper switch for an
indicating transmitter, located on the LCD module, can be set to the
right (fail down i.e. ≤ 3.75 mA) or left (fail up i.e. ≥ 21.75 mA). For
non-indicating transmitters the jumper switch is located on the main
CPU module, it can be set up (fail up to ≥ 21.75 mA) or down (fail
down to ≤ 3.75 mA). Refer to Figure 3-1 for detailed summary of
jumper settings for both CPU and LCD modules.

Level

Low/Down
High/Up

4~20 mA Saturation

3.9 mA
20.8 mA

4~20 mA Alarm

≤ 3.75 mA
≥ 21.75 mA

P-3100:TEMPLATE  3/1/10  11:27 AM  Page 7

Содержание 3100

Страница 1: ...one 219 879 8000 www dwyer inst com P O BOX 373 MICHIGAN CITY INDIANA 46361 U S A Fax 219 872 9057 e mail info dwyer inst com Specifications Installation and Operating Instructions Series 3100 Explosion Proof Differential Pressure Transmitter ...

Страница 2: ... of Alarm and Security Jumper Procedures 3 7 Configuration of Zero and Span Procedure 3 8 Commissioning on the Bench with HHT Chapter 4 Installation 4 1 Overview 4 2 Safety Messages 4 3 Warning 4 4 Commissioning on the Bench with Hand Held Terminal 4 5 General Considerations 4 6 Electrical Considerations 4 7 Wiring 4 8 Mechanical Considerations 4 9 Environmental Considerations Chapter 5 On line Op...

Страница 3: ...oint 1 1 Using This Manual The operating manual provides information on installing operating and maintaining the Mercoid Model 3100 Smart Pressure Transmitter The Chapters are organized as follows Chapter 2 Handling Cautions Chapter 2 provides instructions on commissioning and operating the Model 3100 Smart Pressure Transmitters Informations on software functions configuration parameters and on li...

Страница 4: ...PC Configurator The transmitter s various variables in host are able to be changed configured and calibrated by users The HART Communication between DC power supply and transmitter requires a 250 550 Ohm resistance 1 3 Software Compatibility The Mercoid Smart Pressure Transmitter s software is implemented at the factory The following functions can be configured using a HHT Hart Communicator Suppor...

Страница 5: ...d vibration are minimal Where the area classification does not exceed the explosion proof rating Where maintenance is easy Where the transmitter can be handled easily Be cautious of process connections leaking 24 VDC Power Supply is 11 9 Vdc 45 Vdc For HART communication resistance on transmitter terminal loop should be between 250 550 Ohms When mounting the transmitter an appropriate bracket shou...

Страница 6: ...Sensor Zero Trim apply a pressure for zero in advance Sensor Zero Trim the sensor when the pressure is sufficiently stabilized after approximately 10 seconds 3 There are two ways to pressure zero One way is to apply zero differential pressure making pressure the same on both the high and low side The other is to close High and Low side of a 3 valve manifold and open the equalizing valve 4 Sensor Z...

Страница 7: ...stomer use metal conduit wiring or twisted pair shield cable for signal wiring to conform with EMC regulation when installing the Mercoid 3100 transmitters Chapter 3 Transmitter Functions 3 1 Overview This Chapter contains information on operating the Model 3100 Tasks that should be performed on the bench prior to installation are explained in this chapter 3 2 Safety Message Procedures and instruc...

Страница 8: ...ers are protected 2 Physically removing Zero and Span Magnetic Buttons you are unable to regulate zero and span locally 3 5 1 Security Jumper EEPROM Write Protect Prevents the transmitter s configured parameters from being changed 3 5 2 Zero and Span Buttons By removing the Magnetic Buttons you can t configure the transmitter using the Zero and Span locally 3 6 Configuration of Alarm and Security ...

Страница 9: ...select 3810 Select increasing rate 1000 Increase 3 times Select increasing rate 100 Increase 8 times Select increasing rate as 10 Increase 1 time C To select the increase decrease steps SelInc message will be displayed on the bottom of the LCD Select parameter and press the Zero button The decimal value will be changed when the Zero button is pressed After set press the span button to execute the ...

Страница 10: ... button until the Decimal Place message appears the decimal place will appear on the second line of the LCD as follows 7 The first line on the LCD will display 0 0 8 The Decimal Place can be changed by pressing the Zero button Save the setting by pressing the Span button after the decimal place has been selected 9 The set value will display the PV value and Engineering value 10 The LCD will displa...

Страница 11: ...an be commissioned before and after installation Commissioning is easier if the transmitter is configured on a bench with an HHT before installation 4 5 General Considerations The transmitter can be mounted near the process to minimize piping Keep in mind that easy access is required for personnel field calibration and installation Install the transmitter in an area with minimal vibration shock an...

Страница 12: ...t the process wires to the transmitter 4 7 3 Connecting External Wires to Transmitter Terminal Box 1 Open the cover indicated FIELD TERMINAL Do not open the cover if the transmitter is located in an explosion proof area and powered Connect the power supply to the terminal indicated PWR left terminal and in the central terminal Do not connect power supply to terminal TEST It will damage the test di...

Страница 13: ...e below 10 ohms Note In case of Built in Lightening Protector Grounding should satisfy Special KS requirements grounding resistance 10 ohm or less b There are ground terminals on the inside and outside of the transmitter Either of these terminals may be used c Use 600V insulated PVC wire for grounding 4 7 6 Power Supply Voltage and Load Resistance When configuring the loop make sure that the exter...

Страница 14: ...n in Hazardous Location The transmitter is designed with an explosion proof housing Installation environment must not exceed the explosion proof rating Chapter 5 On Line Operation 5 1 Overview This chapter describes how to configure the 3100 Smart Pressure Transmitter The transmitter can be configured in On Line or Off Line mode In On Line Mode a compatible HHT or PC configuration device must be u...

Страница 15: ...bic feet hectoliters 5 5 3 4 20mA Configuration Set the Zero and Span for the 4 20mA analog output 5 6 Detailed Setup 5 6 1 Set Fail Mode When the sensor or microprocessor is not operating properly the transmitter will output 3 75mA or 21 75mA based on the Fail Mode setting 5 6 2 Set Dampening Time The Dampening Seconds value changes the response time of the transmitter to smooth out variations ca...

Страница 16: ...im when first commissioning the transmitter on site There are three ways to trim the sensor Sensor zero trim full trim and zero adjustment Sensor zero trim is a one point adjustment typically used to compensate for the mounting position Two point trim is a full sensor trim in which two accurate pressures are applied equal to or greater than the range values and the output is linear You should alwa...

Страница 17: ...for a 250 550 ohms resistance between the power supply and HHT Check for adequate voltage to the transmitter the transmitter requires 11 9 45 Vdc Check for intermittent shorts open circuits and multiple grounds Connect HHT and enter the transmitter test mode to isolate a sensor failure Check for dirty or defective terminals interconnecting pins or receptacles Check the output voltage of the power ...

Страница 18: ...nics module and the other contains all wiring terminals and communication terminal 6 4 2 2 Fail Mode Jumper Switch and EEPROM Write Fail mode jumper switch and EEPROM Write is located behind the front cover Figure 6 2 Structure of Housing Figure 6 3 Structure of Electronics Module Page 17 Figure 6 1 Test Terminals ...

Страница 19: ...lue is over limit 10 Zero Trim done Setting Limit error when executing Zero button function Setting Limit error when executing Span button function Zero button function done Span button function done Zero Adjustment done Configuration completed using buttons Limit error when executing other setting function Over Values for LCD Sensor Code Error Flash Setting Data Reset Flash Setting Data Reset Pro...

Страница 20: ...010 Dwyer Instruments Inc Printed in U S A 3 10 FR RA 443807 00 DWYER INSTRUMENTS INC Phone 219 879 8000 www dwyer inst com P O BOX 373 MICHIGAN CITY INDIANA 46361 U S A Fax 219 872 9057 e mail info dwyer inst com ...

Отзывы: