Installation manual
M-WRG-II ventilation units
- 35 -
Meltem Wärmerückgewinnung GmbH & Co. KG
Am Hartholz 4 · D-82239 Alling
[email protected] · www.meltem.com
VENTILATION THE RIGHT WAY
V E N T I L A T I O N & H E A T R E C O V E R Y
11.3
Checking the air flap on the exhaust air spigot and seals
► Check that the air flap (item 1 in
Fig. 34) on the exhaust air spigot is
correctly seated in the holder (item 2
►
Check that the seals (item 3 in
Fig. 34) around the air spigots on
the back of the ventilation unit are
undamaged. Damaged seals should
be replaced immediately.
NOTICE
— The ventilation unit will not operate
perfectly unless the air flap is
seated correctly.
— For ease of installing the unit (see
section 11.6 on page 36), you
can apply washing-up liquid or
Vaseline to the seals (item 3 in
11.4
Removing the electronics
compartment cover plate
►
Use the screwdriver to loosen the
Torx screw (item 1 in Fig. 35) on the
electronics compartment cover plate
(item 2 in Fig. 35).
►
Remove the electronics compartment
cover plate.
11.5
Threading in cables through the
opening
►
Hold the ventilation unit in front of the
installation location.
►
Thread the mains cable into the
opening (item 1 in Fig. 36) on the
ventilation unit and pull the cable
through the opening.
►
Thread the control cable (if used) into
the opening (item 1 in Fig. 36) on
the ventilation unit and pull the cable
through the opening.
►
Thread the control cable for the
M-WRG-II O/EGG-AUS option (if
used) into the opening (item 1 in
Fig. 36) on the ventilation unit and
pull the cable through the opening.
Fig. 34:
Checking the air flap on the exhaust air spigot
and seals
1
2
3
Fig. 35: Removing the electronics compartment cover
plate
1
2
Fig. 36: Threading in the mains cable and control cable
(if used)
1