Owner’s manual & Technician Settings
Pg. 9
Cont’
Technician settings (Cont’)
temperature
on heaters
sensor
P03 – Upper limit temperature for heating
Press the [SELECT] and [+] buttons simultaneously.
“P03” and the slab upper limit temperature will appear on display.
Use the [+] and [-] buttons to adjust the upper limit temperature.
Range: +41…+122°F / +5…+50°C Default: 86°F / +30°C
*For numbers above 100, “100” will appear on display.
Press the [SELECT] and [+] buttons simultaneously again.
The word “ON” or “OFF” will appear on display.
Use the [+] and [-] buttons enable (ON) or disable (OFF) the P03
parameter.
If disabled, the heaters will work regardless of the upper limit.
Press the [SELECT] and [+] buttons simultaneously again.
The display will show the temperature on the upper limit sensor.
Upper limit
temperature
Set point
enabled
P03
disabled
P02 - Lower limit temperature for heating
Press the [SELECT] and [+] buttons simultaneously.
“P02” and the low limit temperature will appear on display.
When the temperature on the temperature sensor drops below the low
temperature limit, the heating system will stop.
Use the [+] and [-] buttons to adjust the temperature set point.
Range: -40…+23°F / -40…0°C
Default: -31°F / -350°C
Press the [SELECT] and [+] buttons simultaneously again.
The word “ON” or “OFF” will appear on display.
Use the [+] and [-] buttons enable (ON) or disable (OFF) the P02
parameter.
If disabled, the heating system will operate without low temperature
limitations.
Low limit
Temperature
P02
enabled
P02
disabled